EasyManua.ls Logo

Honeywell R7426B - Page 15

Honeywell R7426B
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R7426A,B,C,D TEMPERATURE AND UNIVERSAL INPUT CONTROLLERS
15 63-2565
Fig. 11. Step change responses of proportional,
P+I, and P+I+D controls.
Start Point: O
start
(P.15)
O
start
determines the output O1 midrange shift from the
calculated control point.
R7426A,B,C
O
start
is available on the single output R7426A and the
R7426B when the three floating outputs are configured for
6-stage On/Off sequence control.
Calibrate O
start
in degrees Fahrenheit. It is equal to the offset
(plus or minus) from the set values or calculated control points
at which O1 is at 50 percent.
NOTE: In P+l control, the start point should be set at zero.
R7426D
Calibrate O
start
in percent. It represents deviation from the
control point.
In humidification and dehumidification control, O
start
must be
decreased by 50 percent of the throttling range (Xp1).
EXAMPLE:
Set OCTRF to 1 for reverse control behavior.
Set Xp1 at 6 percent.
Set O
start
at -3 percent.
With these settings:
If the actual humidity value is equal to the calculated
control point CTRP1 (zero deviation), the humidifier
valve will be fully closed.
At 6 percent rh below CTRP1 the valve is fully open.
At 6 percent rh above CTRP1, the controller provides
an output signal of +1200 mV (100 percent) to fully
open the cooling valve for dehumidification.
NOTE: Always set O
start
to the value for proportional
control.
Occupied/Unoccupied Function: SOFFS (P.16)
A potential free contact can be used between terminals 1 and
4 to switch between occupied (contact closed) and
unoccupied (contact open) modes.
Control point calculation:
Occupied mode: Use temperature setpoint (W1).
Unoccupied mode: SOFFS parameter value is added to
(cooling) or subtracted from (heating) the calculated control
point.
Heating and cooling sequence applications: SOFFS value
is added to the control point for cooling (CTRPC) and
subtracted from the control point for heating (CTRPH). See
Fig. 12.
IMPORTANT
Set the R7426A parameter Dir/RevO1 to Dir or Rev
to match the required heating or cooling application.
If parameter Dir/RevO1 is set to Cho (summer/winter
changeover), parameter SOFFS is ignored.
Fig. 12. Sequence control occupied/unoccupied function.
For control point calculation and reference to applications, see
Table 15. Using the table, you can construct the equation to
use for calculating the proper control point.
EXAMPLE:To calculate CNTRPC for temperature cascade
sequence, use Table 15 to construct the formula:
Table 15. Control Point Reference and Calculation
a
Control with Heating, Mixed Air Dampers, or Energy
Recovery and Cooling
M17453
Xw
Xw (%)
(%)
O
0
TIME
TIME
tr
P + I + D CONTROL
P
P
tr
P + I CONTROL
PROPORTIONAL CONTROL
P=
100
Xp
(%/S)
Xw (%)
O
TIME
tr
td
P
P
tr
P=
P x v
d
100
Xp
(%/S)
Main Temperature
Cascade
Temperature
Sequence
a
Temperature
Cascade
Sequence
a
CNTRP1
CNTRPC
CNTRPH
CNTRP2
CNTRPC
CNTRPH
W1 + + + +
XOFFS + +
CPA + + + +
OAT
comp
++++
W
cas
++++
SOFFS +- +-
R
cas
/100 x
(Omaster+50)
----
XP1 / 2 + -
XP2 / 2 + -
O(%)
T
100
M17454
OFFS OFFS
CTRPH CTRP1
UNOCCUPIED
OCCUPIED
XpH XpC
CNTRPC W
cas
OFFS
R
cas
100
----------
Y
master
50+()×
XP2
2
-----------
++=

Other manuals for Honeywell R7426B

Related product manuals