INSTALLATION INSTRUCTIONS
Put Bar Code Here
66-1089-11
EC7890A1037,
RM7890A1064 or
RM7890B1055 only.
SIL
3
Capable
RM7890A,B,C/EC7890A,B
7800 SERIES Relay Modules
APPLICATION
The Honeywell RM7890A,B,C/EC7890A,B Relay Modules are
microprocessor based integrated burner controls for on/off
automatically fired gas, oil, or combination fuel single burner
applications. The RM/EC7890 Relay Module is intended to
replace the RA890F,G, H Protectorelay® Primary Control. The
RM/EC7890 System consists of a relay module, subbase, and
amplifier. Options include keyboard display module (KDM),
and remote display mounting.
Functions the RM/EC7890 provides include automatic burner
on/off sequencing, flame supervision, system status
indication, system or self-diagnostics and troubleshooting.
This document provides installation and static checkout
instructions. Other applicable publications are:
65-0084: Q7800A,B 22-Terminal Wiring Subbase Product
Data.
65-0090: S7800A Keyboard Display Module Product Data.
65-0091: S7810A Data ControlBus Module™ Product Data.
65-0095: S7820 Remote Reset Module Product Data.
65-0097: 221729C Dust Cover Packing Instructions.
65-0109: Flame Amplifiers for the 7800 SERIES Product
Data.
65-0131: 221818A,C Extension Cable Assembly Product
Data.
65-0229: 7800 SERIES Relay Modules Checkout and
Troubleshooting.
65-0249:S7810M ModBus Module.
SPECIFICATIONS
Electrical Ratings (See Table 3):
Voltage and Frequency:
RM7890: 120 Vac (+10/-15%), 50/60 Hz (±10%).
EC7890: 220/ 240 Vac (+10%/-15%), 50/60 Hz (±10%).
Power Dissipation: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A maximum, type SC or
equivalent, fast blow.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncondensing.
Vibration: 0.5G environment.
SIL 3 Capable
SIL 3 Capable in a properly designed Safety Instrumented
System. See form number 65-0312 for Certificate Agree-
ment.
Approvals:
RM7890A,B:
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ.
Canadian Standards Association Certified: LR9S329-3.
Factory Mutual Approved: Report No. J.I.1V9A0.AF.
Swiss RE (formerly IRI) : Acceptable.
Federal Communications Commission: Part 15, Class B,
Emissions.
RM7890C:
Underwriters Laboratories Inc.: Component Recognized.
EC7890:
Factory Mutual: Approved.
EC7890A1037, RM7890A1064:, RM7890B1055
Gastec—EN268, Report 115679/1.
Note: RM7890B1055 is rated cULus and CE.
maxon.su
Question and Answer IconNeed help?

Do you have a question about the Honeywell rm7890a and is the answer not in the manual?

Honeywell rm7890a Specifications

General IconGeneral
ModelRM7890A
Output TypeRelay
Control TypeOn/Off
Frequency50/60 Hz
Number of Outputs1
Housing MaterialPlastic
TypeController
ApplicationIndustrial Control
Voltage24 VAC
Temperature Range-40 to +140 ℉ (-40 to +60 ℃)
Operating Temperature-40°C to 70°C

Summary

Installation Instructions

General Installation Precautions

Covers crucial warnings, handling instructions, and installer qualifications.

Wiring Procedures and Guidelines

Final Wiring and Static Checkout

Static Checkout Procedure

Detailed steps to verify subbase wiring and external component operation.

Static Checkout Tests and Cautions

Static Checkout Table

Step-by-step guide for performing static checkout tests and abnormal condition checks.

Mounting the RM;EC7890 Relay Module

Principal Technical Features

Safety Shutdown (Lockout) Conditions

Lists various conditions that trigger a safety shutdown or lockout.

Sequence of Operation

Describes the operational sequences like Initiate, Standby, Ignition Trials, and Run.

Settings and Adjustments

Selectable Site-Configurable Jumpers

Explains the use and configuration of site-configurable jumpers for specific functions.

Related product manuals