EasyManua.ls Logo

Honeywell RM7838A

Honeywell RM7838A
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
DIRECTIONS:
1. Disconnect all power to control being replaced. Note
that more than one power supply disconnect may be
involved.
2. Remove old control from subbase.
3. Mark all wires on subbase; i.e., wires connected to
terminal 1 should be marked 1.
4. Disconnect wires from subbase.
5. Remove old subbase.
6. Mount Q7800 Subbase.
7. Connect wires to subbase according to wiring conver-
sion for control being replaced. Pay close attention to
footnotes. The triangle symbol
with a number or letter
inside designates a footnote.
8. Install the RM7838A control. Make sure the proper
ST7800 purge card and flame detector have been se-
lected for the application.
9. The RM7838A has one site configurable jumper option
that is used to select the Pilot Flame Establishing Period.
Refer to the RM7838A instructions, form 60-0108, for
assistance and proper selection.
10. Refer to the RM7838A instructions, form 60-0108, for
checkout and start-up.
GENERAL FOOTNOTES:
1 Be sure system is modernized to 120 Vac. The
replacement 7800 SERIES control is 120 Vac.
2 Select subbase.
3 The RM7838A cannot be wired for redundant appli-
cations without external relay logic to isolate the
safety critical loads test of the RM7838.
4 Select proper prepurge card based on the purge
timing of the control being replaced or the external
purge timer.
5 Select proper flame amplifier according to the
cross reference table or to meet the needs of the
application.
6 Select proper flame detector when converting from a
competitive control to Honeywell or if a different
flame detection system is desired; i.e., the old flame
amplifier was flame rectification and the new flame
amplifier is to be ultraviolet. Refer to the product
selection matrix on page 3 to select proper flame
detector.
7 Proper grounding of the green subbase terminal
screw to an electrical earth ground is a MUST for
proper operation of the 7800 SERIES control.
8 NOTE: UL allows only two electrical wires to each
subbase terminal. Wiring information may show
more than two wires to a particular terminal, which
may require an external connection to accomplish the
termination.
9 Select proper site configurable jumper configuration
as required by the application. Refer to the cross
reference table and to Specifications, form 65-0108.
NOTE: Jumper number 1 selects Pilot Flame
Establishing Period.
10 Do not use any unused subbase terminals as a wiring
junction or termination point.
1

Other manuals for Honeywell RM7838A

Related product manuals