INSTALLATION INSTRUCTIONS
32-00199-01
SIL
3
Capable
0063
RM7838C1020 and
RM7838C2020 only
RM7838B,C
7800 SERIES Relay Module
APPLICATION
The Honeywell RM7838B,C is a microprocessor based
integrated burner control for industrial process
modulating semiautomatically fired gas, oil, coal or
combination fuel single burner applications. The
RM7838B,C System consists of a relay module, wiring
subbase, keyboard display module (KDM), amplifier, and
purge card. Options include Data ControlBus Module™,
remote display mounting, and first-out expanded
annunciator.
Functions provided by the RM7838B,C include automatic
modulated High Fire and Low Fire proven Purge, burner
pilot startup with pilot valve hold, a special pilot valve hold
from the Run condition, flame supervision, system status
indication, system or self-diagnostics and
troubleshooting.
The RM7838C differs from the RM7838B as follows:
1. Alarms only on Safety Shutdown.
2. Requires ST7800C Purge Timer.
3. C1004 has 15 second MFEP. C1020 has 5 second
MFEP.
This document covers the following 7800 Series Relay
Modules:
RM7838C1020
RM7838C2020
RM7838C1004
RM7838C2004
RM7838B1013
RM7838B2013
This document provides installation and static checkout
instructions. Other applicable publications are:
SPECIFICATIONS
Electrical Ratings (See Table 4):
Voltage and Frequency: 120 Vac (+10/-15%),
50/60 Hz (±10%).
Power Dissipation:
RM7838B,C: 10W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing Total Connected Load: 15A maximum, type SC or
equivalent, fast blow.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +66°C).
Humidity: 85% relative humidity continuous, noncon-
densing.
Vibration: 0.5G environment.
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instrumented
System. See form number 65-0312 for Certificate
Agreement.
Form
Number Description
32-00110 S7800A2142 4-line LCD Keyboard Display
Module Product Data
32-00166 204729A/C KDM NEMA4 Covers for 4-line
LCD KDM
65-0084 Q7800A,B 22-Terminal Wiring Subbase
Product Data
65-0089 ST7800A Plug-In Purge Timer Installation
Instructions.
65-0090 S7800A Keyboard Display Module Product
Data.
65-0101 S7830 Expanded Annunciator Product Data.
65-0109 R7824, R7847, R7848, R7849, R7851, R7861,
R7886 Flame Amplifiers for the 7800 SERIES
Product Data.
65-0131 221818A Extension Cable Assembly Product
Data
65-0229 7800 Series Relay Modules Checkout and
Troubleshooting Product Data
65-0249 S7810M ModBus Module (For CE , Modbus
module S7810M1029 only).
65-0295 50023821-001/2 KDM NEMA4 Covers for
classic 2-line VFD KDM
Form
Number Description
Question and Answer IconNeed help?

Do you have a question about the Honeywell RM7838B1013 and is the answer not in the manual?

Honeywell RM7838B1013 Specifications

General IconGeneral
TypeRM7838B1013
Frequency50/60 Hz
Control ActionOn/Off
Flame Rod AmplifierYes
Output Voltage24 VAC
ApplicationCommercial and industrial burners
Input Voltage120V AC
Temperature Range-40 to +140°F (-40 to +60°C)
MountingPanel mount
Flame TypeUV, IR
ApprovalsUL, CSA

Summary

APPLICATION

SPECIFICATIONS

INSTALLATION

Mounting Wiring Subbase

Relay Module and Subbase Compatibility

Wiring Subbase

FINAL WIRING CHECK

STATIC CHECKOUT

Mounting RM7838 B,C Relay Module

PRINCIPAL TECHNICAL FEATURES

Safety Shutdown (Lockout)

Conditions that trigger a safety shutdown sequence.

OPERATION

Sequence of Operation

Outlines the burner sequence states and timings.

RunTest Switch

SETTINGS AND ADJUSTMENTS

Selectable Site-Configurable Jumpers

Details on setting jumpers for specific configurations.

SAFETY AND SECURITY

Related product manuals