74-3450—2 10
Rooftop Unit Diagnostics Data
Heat Failure: heating alarm status, off = no alarm
BuildngVw —> Rooftop Unit Diagnostics
Cool Failure: cooling alarm status, off = no alarm
BuildngVw —> Rooftop Unit Diagnostics
Economizer Failure: economizer alarm status, off = no alarm
BuildngVw —> Rooftop Unit Diagnostics
Low Static Pressure Failure: static pressure alarm status,
off = no alarm
BuildngVw —> Rooftop Unit Diagnostics
Zone Data
Room Temperature: room temperature of selected zone
BuildngVw —> Zone Data —> Zone Name
Control Setting: room temperature setpoint of selected zone
BuildngVw —> Zone Data —> Zone Name
press ChngValue to modify
Occupancy Status: indicates current setpoint Occupied or
Unoccupied
BuildngVw —> Zone Data —> Zone Name
press Override to modify
Operating Mode: current mode heat or cool
BuildngVw —> Zone Data —> Zone Name
Damper Position: zone damper position as % open
BuildngVw —> Zone Data —> Zone Name