TFI 812
Gas Burner Control Box
INTRODUCTION
The TFI 812.2 gas burner control boxes are capable of
controlling and monitoring atmospheric gas burners. They
have been tested and approved as per DIN 4788 part 3
edition 04.89 and with the European standard EN 298. They
are also suitable for use with stationary warm air generators
(as per DIN 4794).
The control boxes are designed for maximum safety in case
of fluctuations in the voltage supply. If the mains voltage
drops below the permitted level, operation is interrupted
and the control box automatically prevents the start sequence
from being repeated. In this way, the safety of the system is
not put at risk by a drop in the mains voltage.
The control box and the monitoring function which it performs
is not negatively affected by occasional stray ignition sparks
jumping to the ionisation electrode.
The FR 870 remote reset (item no. 70700) can be connec-
ted, and allows remote reset of the control box (see doc.
no. 750).
The TFI 812 mod.5 can be installed in place of the TFI
712 F, and the TFI 812 mod.10 can be employed to replace
the TFI 712.
It is not necessary to rewire or replace the baseplate. The
difference in the heights of the units can be compensated by
attaching the reset button extension (item no. 70601).
The difference between the TFI 812.1 and the TFI 812.2 is
that the TFI 812.2 control boxes are equipped with the
voltage drop fail-safe function. Otherwise, they are identical
in terms of operation and possible applications.
CONSTRUCTIONAL FEATURES
The control box is well protected by a flame-resistant,
transparent, plug-in type plastic housing which encloses
the thermo-mechanical temperature-compensated timing
unit, the flame monitoring unit and the reset device.
The reset button, which incorporates an indicator lamp, and
the central screw fastening, are situated on the upper part
of the control box.
The baseplate, which can be equipped with additional
terminals, together with the various optional cable entry
points, makes universal wiring possible.
For 2-stage atmospheric gas burners
Possible flame detectors:
- Ionisation probe
- Infra-red flicker detector
TYPES AVAILABLE
TFI 812.2 mod. 5 Safety interval nominal 5 sec.
Pre-ignition time approx. 15 sec.
appropriate nominal capacity
according to the appliance standort
or the gas appliance directive.
TFI 812.2 mod. 10 Safety interval nominal10 sec.
Pre-ignition time approx. 10 sec.
appropriate nominal capacity
according to the appliance standort
or the gas appliance directive.
TFI 812.2 B mod. 5 dito – without Pre-ignition time
TFI 812.2 B mod. 10 dito – without Pre-ignition time
TECHNICAL DATA
Supply voltage 220 / 240 V (-15... +10%)
50 Hz (40 - 60 Hz)
Fuse rating 10 A rapid or 6 A slow
Power consumption 5 VA
Max. current per
output terminal 4 A
Max. current total 6 A
Pre-ignition time 15 or 10 sec.
Delay, post-ignition time none
Safety interval nominal 5 or 10 sec.
Safety interval max. 10 or 20 sec.
2nd stage delay approx. 20 sec.
Reset delay after lockout approx. 60 sec.
Permissible ambient temperature -20° C to +60° C
Sensitivity 1.5 µA
Min. ionisation current required 2 - 3 µA
Ionisation probe insulation probe - earth
greater than 50 M
Stray capacitance probe - earth
less than 1000 pF
(max. 20 m cable)
Insulation standard IP 44
Weight incl. baseplate 250 g
Mounting attitude any
EN1C-0143SZ20 R0305
Distribuitor:
FLAME POWER SRL
021-3121727 ; 0744-340566
contact@arzatoare.ro ; www.arzatoare.ro
Question and Answer IconNeed help?

Do you have a question about the Honeywell Satronic TFI 812 Series and is the answer not in the manual?

Honeywell Satronic TFI 812 Series Specifications

General IconGeneral
CategoryControl Unit
TypeTFI 812 Series
BrandHoneywell Satronic
Protection ClassIP40
Mains Frequency50/60 Hz
Prepurge TimeAdjustable
Safety Time3 s
ApplicationIndustrial burners
Input Voltage230 V AC
Operating Temperature-20...+60 °C
Flame DetectorIonisation probe or UV flame detector
Relative HumidityMax. 95% (non-condensing)

Summary

Satronic TFI 812 Gas Burner Control Box Introduction

Available TFI 812 Models and Features

Details the different TFI 812 models available and their specific features and applications.

Technical Data for TFI 812 Control Box

Provides a comprehensive list of technical specifications including supply voltage, fuse rating, and current limits.

Technical Features and Safety Guidelines

Flame Detection Methods and Requirements

Explains suitable flame detectors like ionization probes and IRD flicker detectors and their installation.

Safety Conformance and Installation Procedures

Covers safety standards compliance and detailed instructions for baseplate and general installation.

Commissioning, Maintenance, and Faults

Important Notes for Commissioning and Maintenance

Highlights critical checks for wiring, fuse ratings, and safety shutdown procedures before operation.

Routine Checks and Fault Identification

Describes necessary routine checks and lists common faults like burner non-start or lockout.

Wiring Diagrams and Detector Connections

TFI 812.2 Wiring and Sequence Diagrams

Presents detailed wiring diagrams, sequence of operation, and component labels for the TFI 812.2.

IRD Detector Connection Specifications

Details the specific wiring connections required for the IRD 1020.1 flame detector.

Dimensional Data and Ordering Information

Dimensions of TFI 812 Control Box and Baseplate

Provides detailed drawings and measurements for the TFI 812 control box and its baseplate.

Flame Signal Measurement and Product Ordering

Explains how to measure the flame signal and lists available items with their designations and item numbers.

Related product manuals