SCS Series Manual — P/N 15712:L 7/18/16 61
Configuration The SCSSCE
Toggle Switch Operation for FSCS Mode
FSCS ON/AUTO/OFF (OPEN/AUTO/CLOSED) Toggle Switch Operation
Each ON/AUTO/OFF toggle switch will function according to Table 3.6 for non-alarm conditions and Table 3.7 for alarm conditions. Plac-
ing a toggle switch in the ON or OFF position will activate/deactivate the control points as shown. Once this has occurred, further control-
by-event processing at the FACP is inhibited.
NOTE: The AUTO position column in the table indicates the control module (CM) condition when the control panel is in a normal, non-
alarm condition.
SWITCH
GROUP TYPE
FSCS NON-DEDICATED SYSTEM TOGGLE SWITCH POSITION
ON AUTO OFF
1 Deactivates CON
OFFCL
CM Deactivates CON
OFFCL
CM Activates CON
OFFCL
CM
2 Deactivates CON
OFFCL
CM Deactivates CON
OFFCL
CM Activates CON
OFFCL
CM
3 Deactivates CON
OFFCL
CM Deactivates CON
OFFCL
CM Activates CON
OFFCL
CM
4 Activates CON
ONOP
CM Deactivates CON
ONOP
CM Deactivates CON
ONOP
CM
5 Activates CON
ONOP
CM Deactivates CON
ONOP
CM Deactivates CON
ONOP
CM
6 Activates CON
ONOP
CM Deactivates CON
ONOP
CM Deactivates CON
ONOP
CM
7 Activates CON
ONOP
CM
Deactivates CON
OFFCL
CM
Deactivates CON
ONOP
CM
Deactivates CON
OFFCL
CM
Deactivates CON
ONOP
CM
Activates CON
OFFCL
CM
8 Activates CON
ONOP
CM
Deactivates CON
OFFCL
CM
Deactivates CON
ONOP
CM
Deactivates CON
OFFCL
CM
Deactivates CON
ONOP
CM
Activates CON
OFFCL
CM
9 Activates CON
ONOP
CM
Deactivates CON
OFFCL
CM
Deactivates CON
ONOP
CM
Deactivates CON
OFFCL
CM
Deactivates CON
ONOP
CM
Activates CON
OFFCL
CM
SWITCH
GROUP TYPE
FSCS DEDICATED SYSTEM TOGGLE SWITCH POSITION
ON AUTO OFF
1-9 see above depends on CBE after Reset (see
Automatic Control in Dedicated
System Operation section)
see above
Table 3.6 FSCS Toggle Switch Functions (Non-Alarm Condition)
Table 3.7 FSCS Toggle Switch Functions (Alarm Condition)
SWITCH
GROUP TYPE
FSCS NON-DEDICATED SYSTEM TOGGLE SWITCH POSITION
ON AUTO OFF
1 Deactivates CON
OFFCL
CM depends on CBE after Reset Activates CON
OFFCL
CM
2 Deactivates CON
OFFCL
CM depends on CBE after Reset Activates CON
OFFCL
CM
3 Deactivates CON
OFFCL
CM depends on CBE after Reset Activates CON
OFFCL
CM
4Activates CON
ONOP
CM depends on CBE after Reset Deactivates CON
ONOP
CM
5Activates CON
ONOP
CM depends on CBE after Reset Deactivates CON
ONOP
CM
6Activates CON
ONOP
CM depends on CBE after Reset Deactivates CON
ONOP
CM
7Activates CON
ONOP
CM
Deactivates CON
OFFCL
CM
depends on CBE after Reset Deactivates CON
ONOP
CM
Activates CON
OFFCL
CM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell SCS-8 and is the answer not in the manual?

Honeywell SCS-8 Specifications

General IconGeneral
BrandHoneywell
ModelSCS-8
CategoryControl Unit
LanguageEnglish

Related product manuals