10 5496 Intelligent Power Module Manual — P/N 151276-L8:F2 2/15/2022
Installation Earth Fault Resistance
3.2 Earth Fault Resistance
Table 3.2 lists the earth fault resistance detection for each applicable terminal on the FACP.
3.3 Wire Routing
You must follow power-limited wiring techniques, which include maintaining one-quarter inch spacing between power-limited and non-
power limited circuits and separating high and low voltage circuits.
9 - I/O 1 Output circuit
*
24 VDC 3.0 A Notification Circuits
10 +
11 - SBUS SBUS power 24 VDC 1.0 A
12 +
13 A SBUS communication 5 VDC 100 mA
14 B
* Regulated/special application when used for releasing.
Terminal # and Label Description
Rating
Voltage Current
Table 3.1 Terminal Strip Description and Electrical Ratings
Function Terminal Number Terminal Label Value (in ohms)
Battery 1 - BATTERY 0
2+ 0
Notification Appliance Circuit 4 3 H4- OUT4 0
4H4+ 0
Notification Appliance Circuit 3 5 H3- OUT3 0
6H3+ 0
Notification Appliance Circuit 2 7 H2- OUT2 0
8H2+ 0
Notification Appliance Circuit 1 9 H1- OUT1 0
10 H1+ 0
Table 3.2 Earth Fault Resistance Values by Terminal
B
W
BATTERY
12
–+
3
975
4
1086
OUT4
OUT1OUT2
OUT3
H4–
H1–H2–
H3–
H4+ H1+H2+H3+
11
12
13 14
SBUS
S– S+ A
B
ON
12345
6
5496 board
to SBUS
to NACs
batterybattery
to AC power
Figure 3.2 Wire Routing