5496 Intelligent Power Module Manual — P/N 151276-L8:F2 2/15/2022 9
Section 3: Installation
The 5496 installation involves the following steps:
Connect the AC power (see Section 3.4) and the backup battery (see Section 3.5).
Make physical connection to a Silent Knight addressable FACP (see Section 3.6).
Set an ID for the 5496 (see Section 3.6.1).
Make physical connection to any outputs that will be powered by this 5496. See Section 3.7 for notification appliance wiring
information. Refer to Silent Knight addressable FACP Installation Manuals for software configuration information and other
information about installing outputs. Silent Knight Addressable FACP Installation Manuals can be found on Silent Knight’s website at
www.silentknight.com.
3.1 5496 Board and Terminal Strip Description
Figure 3.1 shows the 5496 circuit board including the location of terminals and the DIP switch for setting the module ID.
Table 3.1 describes the 5496 connections and provides electrical ratings where appropriate.
Terminal # and Label Description
Rating
Voltage Current
B AC input (hot) 120 VAC, 60 Hz 2.7 A
Earth ground N/A N/A
W AC input (neutral) 120 VAC, 60 Hz 2.7 A
1 - Battery Battery 24 VDC 0.75 A
2+
3 - I/O 4 Output circuit
*
24 VDC 3.0 A Notification Circuits
4+
5 - I/O 3 Output circuit
*
24 VDC 3.0 A Notification Circuits
6+
7 - I/O 2 Output circuit
*
24 VDC 3.0 A Notification Circuits
8+
Table 3.1 Terminal Strip Description and Electrical Ratings
B
W
BATTERY
12
–+ 3
97
54
108
6
OUT4
OUT1OUT2
OUT3
H4–
H1–H2–
H3–
H4+
H1+
H2+
H3+
11
12
13 14
SBUS
S– S+ A
B
ON
12345
6
All circuits are supervised,
power-limited, except battery
and AC power which are
supervised, non-power-limited.
Figure 3.1 5496 Board Layout
battery
connections
regulated output
circuits
SBUS
Connections
DIP switches for
setting ID
AC power
connection

Related product manuals