- 2 -  
 
 
TESTING 
Test communications between the detector and the control panel.  The 
detector mode has two test buttons; one for smoke testing and one for 
CO testing. 
 
The detector may also be functionally tested using canned smoke and 
canned CO.  If the detector fails any of the test methods, the detector 
should be replaced. 
NOTE: Testing the detector will activate the alarm and send a signal to the 
panel. Before testing, notify the proper authorities to avoid any 
false alarms.  
Smoke Test  (Alarm Test) 
Press and hold the Smoke Test button for 1 to 2 seconds. The 
detector will sound and illuminate per Table 2 and send a smoke alarm 
signal to the control panel (all programmed smoke detector loops are 
signaled). Verify that the smoke alarm signal was received at the 
control panel.  
Smoke System Test (Functional Smoke Test) 
Press and hold the Smoke Test button for 3 to 5 seconds to enter the 
functional smoke test mode. See Functional Smoke Test section below.
Functional Smoke Test 
With the detector in smoke system (functional) test mode, spray 
canned smoke into the detector. The canned smoke that can be used 
and is approved for test include: Home Safeguard Industries 25S, SDi 
CHEK02 and CHEK06, SDi SOLOA4, and SDi SMOKESABRE. 
1. 
The detector will sound and illuminate per Table 2 and a smoke 
alarm signal will be sent to the panel.   
2. 
Verify the smoke alarm signal was received by the control panel. 
CO Test (Alarm Test) 
Press and hold the CO Test button for 1 to 2 seconds. The control 
panel should display and sound a CO alarm (all programmed CO 
detector loops are sent). 
CO System Test (Functional CO Test) 
Press and hold the CO Test button for 3-5 seconds to enter the 
functional gas test mode. See Functional Gas Test section below.   
Functional Gas Test 
Solo C6 brand canned CO may be used to verify the detector’s ability to 
sense CO by utilizing the RealTest® feature as follows: 
1.  Press and hold the CO test button for 3 to 5 seconds. The green 
LED will start blinking once per second indicating the detector is in 
RealTest® mode. (If the detector will not go into RealTest® mode, 
the CO sensor may be in fault or at end-of-life.) 
2.  While the green LED is blinking once per second, spray a small 
amount of canned CO directly into the CO gas entry port.  
3.  Upon successful gas entry and if functioning properly, the detector 
will go into CO alarm and send an alarm to the control panel. 
4.  The CO test will automatically clear when the CO clears from the 
sensor or in 30 seconds if no CO was introduced. 
 
HUSH FEATURE / ALARM SILENCE
 
If required, the audible alarm for smoke and CO conditions can be 
silenced for 5 minutes by pushing the “Test/Hush” button. In addition, 
low chirping can be silenced for 12 hours when the Test/Hush button is 
pressed.  
During a Smoke alarm, if an alarm condition still exists after the 5 
minute hush period, the alarm will sound.  The hush feature will not 
operate at levels above 4%/ft smoke concentration. 
During a CO alarm, if carbon monoxide is still present after the 5 minute 
hush period, the alarm will sound. The hush feature will not operate at 
levels above 350 ppm (parts per million) carbon monoxide. 
CO SENSOR END-OF-LIFE FEATURE 
When the CO sensor has passed end-of-life, a trouble signal will be 
sent to the control panel (if programmed). This indicates that the CO 
sensor inside the detector must be replaced. If unresolved for 30 days, 
the detector will chirp every 45 seconds. The typical life of the CO 
sensor is ten years from the date of manufacture. It is recommended to 
periodically check the “Replace by” date located on the label on the 
back of the detector head. 
 
 
 
 
CO Test Button
Smoke Test Button
5800 Combo ii -005
Follow
instructions
on the Can
CO Gas Port
Test
Buttons
HEAT
    ≥ 12” 
(30.48 cm)
SMOKE
*
Solo C6
        CO
1
2
3
4
(    ) 
30
0
45
5
~ 5 sec/seg
15
or
(    ) 
 
 
 
 
Table 3: Carbon Monoxide Detector: Events & 
Contact ID Codes 
Event  Alpha Keypad
 
CS Report
 
CO alarms  CO Alarm
 
CO alarm (CID 162)
 
CO test  CO Alarm  CO alarm (CID 162) 
Low battery  Lo Bat 
RF low-battery  
(CID 384) 
Detector 
supervision 
CO Trouble 
RF sensor supervision 
(CID 381) 
Detector end-
of-life/trouble 
CO Trouble 
Sensor trouble - end-
of life (CID 380) 
Tamper 
disarmed = CO Trouble  
armed = CO Alarm
 
RF sensor tamper  
(CID 383) 
 
 
 
Table 2: LED Indication & Sounder during Test and Trouble 
MODE 
Status LED 
(Top) 
Side LED 
Windows 
Sounder
Speaker 
Smoke Test 
Blink Green 
once every 
second 
Dark  Temp-3 
Warning of 
alarm signal  
transmission.  
Voice smoke 
warning 
Smoke System 
(functional) Test 
Blink Red 
once every 10 
secs 
Blink once 
every  
10 secs 
 
 
RealTest™ 
Functional CO  gas 
entry test – Waiting 
for gas entry 
Blink Green 
once per 
second 
Dark  Silent 
Voice 
instructions for 
testing; warning 
of alarm signal 
RealTest™ 
Functional CO  gas 
entry test  -Upon 
successful gas 
entry 
Blink Red 
once every  
10 secs 
Blink blue 
every  
10 secs 
Modified 
Temp-4 
Voice carbon 
monoxide 
warning 
Low Battery 
Blink Amber 
every 10 secs 
Dark 
Chirp 
every 45 
secs 
after 7 
days 
Voice instruc-
tions when 
chirp is 
silenced by 
pressing either 
test button 
Smoke 
Maintenance 
Blink Amber 
every 5 secs 
Dark  Silent 
Voice smoke 
maintenance 
instructions if 
either test 
button is 
pressed 
CO Trouble 
Double Blink  
Amber  every 
5 secs 
Dark  Silent 
 
CO End of Life – 
First 29 days 
Double Blink 
Amber  every 
3 secs 
Dark  Silent 
Voice end-of- 
life instructions 
when either test 
button is 
pressed 
CO End of Life – 
after 30 days 
Double Blink 
Amber every 3 
secs 
Dark 
Chirp 
every 45 
secs 
Voice end-of-life 
 when 
either test button 
is pressed 
Power Up 
Blink Green, 
for 30 secs  
Dark  Silent 
Language set 
instructions only 
on first time 
power-up  
Normal (Standby) 
Single Blink 
Green every 
10 secs 
Dark  Silent 
Silent 
Freeze Warning 
(low temp) 
Blink Red 
every 10 secs 
 
   
 
TESTING SIGNAL STRENGTH 
Perform this test in accordance with NFPA 72 inspection, testing and maintenance requirements to determine a strong communication 
path with the control panel.  
1.   Activate the wireless system’s GO/NO GO TEST mode. 
2.   Press the detector’s Smoke TEST button (•) for 1-2 seconds. The detector should immediately transmit an alarm signal to the control 
panel. The built-in horn will start to sound about 2.5 seconds after pressing the button.  
3.   The wireless system’s keypad should emit at least three beeps when the alarm transmission is received and display the transmitting 
detector’s zone number.  
4.   When the console has received the test signal, the horn will stop and a few seconds later the detector’s zone number will clear from 
the console display.  
5.   If the console does not respond as noted, and if this is an initial installation, try moving the detector to another location that provides 
proper reception. Also be sure that the detector has been “enrolled” by the control panel (see Enrollment section). Then, repeat the 
test. 
6.   Turn off the system’s TEST mode (typically security code + OFF).