Application Note:
Fire-Lite IPDACT Setup for Installing Dealers
These pictorial instructions should be used in conjunction with the formal
PID (Product Installation Document) included with the IPBRKT or IPENC as
well as the instructions included with the IPDACT. Please Read all
documentation prior to performing any installation or programming.
Installation Instructions for use with HyperTerminal™ and serial port
Parts List
Part Numbers Description
IPDACT Internet Communicator-Contact ID only.
Requires compatible FL panel equipped
with on-board or optional DACT. Requires
300mA aux non-reset able power from
FACP. Includes cable from panel primary
telco port to IPDACT.
IPBRKT Bracket for mounting IPDACT inside MS-
9200UDLS common enclosure or in
optional HPP-300ULX power supply
IPSPLT Splitter for dual phone lines to IPDACT
input cable.
ALMSC119 RJ45-DB9F PC serial port programming
cable for IPDACT.
IPENC Optional cabinet for mounting IPDACT next
to compatible Fire-Lite FACP. Use when
connecting to older non common enclosure
panels such as MS-9200UD or MS-9600.
Includes IPBRKT mounting bracket already
installed.
HP300ULX Optional UL listed Fire Aux power supply for
mounting IPDACT next to compatible Fire
Panel when additional power is required for
IPDACT.
Question and Answer IconNeed help?

Do you have a question about the Honeywell Smoke Alarm and is the answer not in the manual?

Honeywell Smoke Alarm Specifications

General IconGeneral
Alarm Sound Level85 dB at 10 feet
Hush FeatureYes
Test ButtonYes
Power SourceBattery
Sensor TypePhotoelectric
LED IndicatorYes
Operating Temperature40°F to 100°F (4°C to 38°C)
DimensionsVaries by model
WeightVaries by model

Summary

Parts List

IPDACT

Internet Communicator-Contact ID only. Requires compatible FL panel with power and telco port.

IPBRKT

Bracket for mounting IPDACT inside MS-9200UDLS common enclosure or HPP-300ULX power supply.

IPSPLT

Splitter for dual phone lines to IPDACT input cable.

ALMSC119

RJ45-DB9F PC serial port programming cable for IPDACT.

IPENC

Optional cabinet for mounting IPDACT next to compatible Fire-Lite FACP for older panels.

HP300ULX

Optional UL listed Fire Aux power supply for mounting IPDACT when additional power is required.

Mounting Options

Using Common Enclosure

Connect the IPDACT to compatible fire panels by installing the IPBRKT into the common enclosure cabinet.

Installation using IPENC or HP300ULX

Mounting IPBRKT inside HP300ULX

Mount the IPBRKT within the HP300ULX enclosure to provide additional power for the IPDACT.

Programming the IPDACT

HyperTerminal Setup and Connection

Configure HyperTerminal settings and establish a serial connection to the IPDACT.

Returning IPDACT to Factory Default Settings

Steps to reset the IPDACT to its factory default configuration using a jumper and power cycle.

Quick Install Configuration

Configure IPDACT network settings (DHCP, IP address, Gateway, Account Number) via HyperTerminal.

Register MIP with Central Station

Register the IPDACT module with the Central Station receiver using specific installation password.