Installation using 411UD for monitoring Alarm, Trouble and 
Supervisory dry contacts from any FACP 
 
The 411UD can also be mounted next to the IPDACT inside the HP300ULX and 
used to monitor the Alarm, Trouble, and Supervisory dry contacts from any 
manufacturer’s fire alarm control panel.  Please see the product installation 
document shipped with the IPBRKT for details on mounting and wiring. 
 
Programming Instructions Using HyperTerminal 
 
The IDPACT will be programmed from a personal computer (PC) using Windows 
HyperTerminal. This program can typically be found in the accessories directory 
of Windows™ programs. The black serial cable (PN: ALMSC119) described 
above is needed between a PC COM port and “CN1” on the IPDACT. 
 
Returning the IPDACT to factory default settings:  
Note: While not a required step, it is always good practice to insure any 
programmable device be set to its default factory settings.  To return the IPDACT 
to factory default settings, follow the procedure below: 
 
1.  Remove power to IPDACT. 
2.  Short jumper P2 on the IPDACT using the supplied jumper. 
3. Reapply power 
4.  LEDs LD1 through LD5 will light in succession once and then start again a 
second time 
5.  During second cycle, remove jumper from P2 
6.  After LEDs cycle through a third sequence, the IPDACT has been 
returned to Factory settings. LED "LD6" should be off. 
 
Run HyperTerminal: 
•  Create a NEW connection.  Give it a name that you can remember.  The 
sample shown below is called IPDACTSERIAL.