TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS
62-0278—13 14
19 Remote Setback 0 Disabled
1 Hotel card enabled N.O. for unoccupied mode with
1 second software delay going from UnOccupied to
Occupied;
2 minute delay going from Occupied to UnOccupied.
2 Hotel Card enabled N.C. for unoccupied mode with
1 second software delay going from UnOccupied to
Occupied;
2 minute delay going from Occupied to UnOccupied.
3 Hotel Card enabled N.O. for unoccupied mode with
1 second software delay going from UnOccupied to
Occupied;
30 minute delay going from Occupied to
UnOccupied
4 Hotel Card enabled N.C. for unoccupied mode with
1 second software delay going from UnOccupied to
Occupied;
30 minute delay going from Occupied to
UnOccupied.
5 Button Press (Default) Press and hold “Heat/Cool/
Off” button for 3 seconds
and thermostat will go into
“Economy Setback”
20 Remote Setback for
Heating
50 to
70
Range is 50°F to 70°F. Default is 64°F. Used when the thermostat
is in the Unoccupied state.
21 Remote Setback for
Cooling
72 to
90
Range is 72°F to 90°F. Default is 79°F.
22 Activity Sensing 0 Disabled (Default) This will be selectable when
IS 19 is set to option 0 or 5.
If IS 19 is configured for
N.O or N.C, activity sensing
will not be available.
1 4 hour sensing
2 8 hour sensing
3 12 hour sensing
4 16 hour sensing
5 20 hour sensing
6 24 hour sensing
23 Freeze Protection 0 Disabled This feature can not
activate when the
application is Cool only.
1Enabled (Default) – Stat cycles On Heat when room
temperature reaches 40°F (4°C), and disables Heat
when room temperature reaches below 46°F (8°C).
The LCD displays FREEZE PROTECT
24 Auto Fan Reset 0 Inactive (Default) Auto Fan Reset is not
allowed (does not display)
when the fan control type is
set to Auto Only, (IS 9 -
value 1).
1 Resets back to Auto after 2 hours. The start time is
calculated after the initial call for Heat/Cool is
satisfied. Then, the two (2) hour timing begins.
2 Resets back to Auto after 4 hours. The start time is
calculated after the initial call for Heat/Cool is
satisfied. Then, the four (4) hour timing begins.
25 Purge Cycle
Frequency
0 No periodic purge (other purges still apply) Option 1 Default is normally
recommended to make sure
changeover is detected
quickly on spring and fall
days.
1 Purge every 2 hours (Default)
2 Purge every 24 hours
Table 4. Installer Setup (IS) Codes and Options. (Continued)
IS
Code Code Description
Option
Value
Option Description (Default value shown in
Bold) Notes