TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS
5 62-0278—13
Fig. 3. Mounting sub-base and thermostat using the adaptor plate (50033847-001).
Terminal Wiring
Table 3 provides the terminal wiring for each model and
application.
NOTE: The TB6575A1000, TB6575B1000 and
TB6575C1000 models have color coded fly
leads attached to the terminals. Refer to
Table 3 for the color codes.
The Terminal identifiers in Table 3 have the following
meaning:
C: Common 24 Vac
Gh: High speed fan relay
Gl: Low speed fan relay
Gm: Medium speed fan relay
L: Line voltage power (120/240/277 Vac)
N: Line voltage ground (120/240/277 Vac)
Ps: Pipe sensor (optional)
R: 24 Vac power
Rs: Remote sensor (optional)
SB: Remote setback (optional)
Sc: Ground (required if remote sensor, pipe sensor,
and/or remote setback are connected)
W/Y: W = Heating; Y = Cooling (2 pipe only)
Y/A: Y = Cooling; A = Electrical heater output
M27591
INSERT SCREW
TO LOCK MAIN
BODY TO
SUB-BASE
SNAP MAIN BODY
ONTO SUB-BASE
SUB-BASE
MOUNT ADAPTOR PLATE ONTO
4X4 WIRING BOX OR 2X4
VERTICAL JUNCTION BOX
USING TWO SCREWS
ADAPTOR
PLATE
SCREW HEAD
COVER
ADAPTOR
PLATE
MOUNT SUB-BASE
ONTO WALL PLATE
USING TWO SCREWS
NOTE: MIDDLE HOLES OF ADAPTOR PLATE ARE USED FOR MOUNTING
TO A 2X4 VERTICAL JUNCTION BOX. USE OUTER HOLES FOR
MOUNTING TO A 4X4 WIRING BOX.