T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
39 63-2605—09
a
The Factory defaults listed here apply to all subbase models with the exceptions of the items listed in Table 21.
b
12:00 Noon is the default start point when time is unknown.
Dehumidification
Min On Time
5 X Minimum on time used with “Dehumidify Minimum On”. Range: 5 to 15
minutes.
Dehumidification
Reset Temp
None X X None: No Reset dehumidification; Enable: Dehumidification using Reset.
Dehumidification
Reset Temp Setpt
2° F X Amount of reset used with “Dehumidify Reset”. Range: 1 to 5° F.
Must be smaller than occupied zero energy band (ZEB) or standby ZEB.
Dehumidification
Reheat
None X X None: No Reheat dehumidification; Enable: Dehumidification using Reheat.
Dehumidification
High Limit
65% X
X
c
Dehumidification High Limit. Range: 10 to 90%.
Clock Year 1999 X Range: 2000 to 2035.
Clock Month 12 X 1: January… 12: December.
Clock Day Wed X Day of the Week: Sun, Mon, Tue, Wed, Thu, Fri, Sat
Clock Minutes
11:15 p.m.
b
X X 12:00 a.m.: Midnight (first minute of the day); 12:00 p.m.: Noon.
Holiday Month 0 X Unprogrammed; January…December.
Holiday Day 0 X Unprogrammed; 1; 2…31; LASTDAYOFMONTH…LAST_SAT
Holiday Duration 0 days X Duration of given Holiday (in days). Range: 0 to 99 days.
Delays On X X On: Delays (on relays, sequential start, etc.) are active.
Off: Delays disabled (also called Test Mode).
System Switch Auto X X System settings: Auto; Cool; Off; Heat; Emergency Heat (valid if Heat Pump)
Fan Switch On X X Fan setting: On; Auto
Occupied Heat
Setpt Stop
55° F X Occupied Minimum Heat Setpoint: Lowest the programmed occupied heating
setpoint can be adjusted. Range: 40 to 90° F; Value OccHt OccCl - 2° F.
Occupied Cool
Setpt Stop
85° F X Occupied Maximum Cool Setpoint: Highest the programmed occupied cooling
setpoint can be adjusted. Range: 45 to 99° F. Value OccCl OccHt + 2° F.
Not Occupied Heat
Setpoint
55° F X X Not Occupied heating setpoint. Range: 40 to 90° F.
UnoccHt OccHt OccCl - 2° F; UnoccHt StdByHt StdByCl - 2° F
Standby Heat
Setpoint
67° F X
d
Standby heating setpoint. Range: 40 to 90° F.
Occupied Heat
Setpoint
70° F X X Occupied heating setpoint. Range: 40 to 90° F.
Occupied Cool
Setpoint
75° F X X Occupied cooling setpoint. Range: 45 to 99° F.
Standby Cool
Setpoint
78° F X
d
Standby cooling setpoint. Range: 45 to 99° F.
Not Occupied Cool
Setpoint
85° F X X Not Occupied cooling setpoint. Range: 45 to 99° F.
UnoccCl OccCl OccHt + 2° F; UnoccCl StdByCl StdByHt + 2° F.
Event 1 State Occupied X X Day Schedule is a structure of 8 days of 4 events each day. Defaults listed are
for Monday through Friday. Saturday/Sunday/Holiday default to
Unprogrammed (None / 12:00 a.m.). All Events can be set for: Standby or
None.
Only Events 1 and 3 can be set for Occupied.
Only Events 2 and 4 can be set for Not Occupied.
Note: The Config ID cannot set an event to Standby, but it can change the
time.
Event 2 State Not Occupied X X
Event 3 State None X X
Event 4 State None X X
Event 1 Time 8:00 a.m. X X Scheduled time for event change.
12:00 p.m.: Noon
12:00 a.m.: Midnight
Event 2 Time 10:00 p.m. X X
Event 3 Time 12:00 a.m
(midnight)
XX
Event 4 Time X X
Table 20. Thermostat Setup Options Through PDA. (Continued)
Configuration
Option
Factory
Default
a
PDA
Tool CnfgID Description