T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
13 62-0257—11
Fig. 22. Setup - Sensors - Sensor A - Units.
1.1.1.1. UNITS (°F or °C)
IMPORTANT
This is a global change and affects the unit
values for all temperature parameters on all
displays.
This UNITS screen displays only for Sensor A.
1. From the Sensor A selections, use the and
buttons to highlight UNITS.
2. Press the button to display the temperature units.
3. Use the and buttons to highlight DEG F or
DEG C.
Default: F (Fahrenheit)
4. Press the button to accept the units and return to
the Sensor A selections.
Fig. 23. Setup - Sensors - Sensor A - Calibrate.
1.1.1.2. CALIBRATE (the sensor)
Ensure that the wire size calibration value is within the
limits. See “Temperature Sensor Calibration” on page 8.
1. From the Sensor A selections, use the and
buttons to highlight CALIBRATE.
2. Press the button to display the calibration degree
value.
3. Use the and buttons to increase/decrease the
desired calibration degrees.
Default: 0
Range: +/-10°F (+/-6°C)
4. Press the button to accept the value and return to
the Sensor A selections.
Fig. 24. Setup - Sensors - Sensor A - Label.
1.1.1.3. LABEL (the sensor input)
For a sensor already labeled, the display positions to and
highlights that label.
1. From the Sensor A selections, use the and
buttons to highlight LABEL.
2. Press the button to display the label list.
3. Use the and buttons to scroll through list and
highlight the desired label.
You may need to scroll up or down to view all possi-
ble labels.
4. Use the button to accept the highlighted label
and exit the list.
NOTE: The label names in list order are: Sensor, Boiler,
Outdoor, Duct, Dischrg, Chiller, Room, Supply,
Return, and Animals.
Fig. 25. Setup - Sensors - Sensor A - Exit.
1.1.1.4. Exit Sensor A Setup
Press the button to exit Sensor A selections and return
to the Sensors menu.
- or -
Use the and buttons to highlight EXIT and press the
button.
SETUP
SENSORS
SENSOR A
UNITS
SETUP
SENSORS
SENSOR A
UNITS
SELECT
UNITS FOR
SENSOR A
DEG F
DEG C
M24431
SETUP
SENSORS
SENSOR A
CALIBRATE
ENTER
VALUE TO
CALIBRATE
SENSOR A
SETUP
SENSORS
SENSOR A
CALIBRATE
0.0
F
o
M24432
SETUP
SENSORS
SENSOR A
LABEL
SETUP
SENSORS
SENSOR A
LABEL
SELECT
LABEL FOR
SENSOR A
SENSOR A
BOILER A
OUTDOOR A
DUCT A
DISCHRG A
CHILLER A
ROOM A
M24433
SETUP
SENSORS
SENSOR A
UNITS
CALIBRATE
LABEL
EXIT
M24434