T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
62-0257—11 14
Fig. 26. Setup - Sensors - Sensor B Menu.
1.2.1. SENSOR B
For two-sensor reset control, Sensor B must always be 
the controlling temperature. For example, in a reset 
control based on outside temperature, Sensor B must be 
the outside sensor.
1. From the Sensors menu, use the  button to high-
light SENSOR B.
2. Press the   button to display the Sensor B menu.
3. Repeat the selections described in “1.1.1. SENSOR 
A” through “1.1.1.4. Exit Sensor A Setup” beginning 
on page 12.
Continue with “1.3. Setting up the Outputs”.
Fig. 27. Setup - Outputs Menu.
1.3. Setting up the Outputs
1. From the Setup menu, use the and  buttons to 
highlight OUTPUTS.
2. Press the  button to display the Outputs menu
3. Continue with “1.3.1. Number of RELAYS”.
Fig. 28. Setup - Outputs - Number of Relays.
1.3.1. Number of RELAYS 
1. From the Outputs menu, use the and  buttons 
to highlight # RELAYS.
2. Press the  button to display the number of relays.
3. Use the  and  buttons to select the number of 
relays depending on setup. (See note below.)
4. Press the  button to accept the value and display 
the Outputs menu.
IMPORTANT
If you change the number of relays, the control-
ler resets the number of relays per loop to zero 
(0) for all loops. You must use Setup mode to 
reconfigure all loops and additional relays.
NOTE: Up to two T775S Expansion Modules can be 
connected to a T775L, making the following out-
puts available:
T775L: 4 relay outputs
T775L with one T775S module: 8 relay outputs
T775L with two T775S modules: 12 relay outputs
SETUP
 SENSORS
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
M24435
SETUP
  OUTPUTS
SETUP
OUTPUTS
# RELAYS
# LOOPS
OPTIONS
LOOP 1
LOOP 2
RELAY 9
RELAY 10
EXIT
APP TYPE:
SEQUENCER
M24436
SETUP
  OUTPUTS
  # RELAYS
SELECT
NUMBER OF
AVAILABLE
RELAYS
SETUP
OUTPUTS
# RELAYS
1 RELAY
2 RELAYS
3 RELAYS
4 RELAYS
8 RELAYS
12 RELAYS
M24437