EasyManuals Logo
Home>Honeywell>Control Unit>TC Series

Honeywell TC Series User Manual

Honeywell TC Series
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
TC · Edition 08.17 35
Function
3.4 Leakage rate Q
L
If no leakage rate is specified, we recommend the max.
possible test period/measurement time is set.
It is possible to check a specific leakage rate Q
L
using
the TC. Within the scope of the European Union, the
maximum leakage rate Q
L
is 0.1% of the maximum flow
rate Q
(n)
max.
[m
3
/h].
Leakage rate Q
L
[l /h] =
Q
(n) max.
[m
3
/h] x 1000
1000
If a small leakage rate Q
L
is to be detected, a long test
period/measurement time must be set.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell TC Series and is the answer not in the manual?

Honeywell TC Series Specifications

General IconGeneral
BrandHoneywell
ModelTC Series
CategoryControl Unit
LanguageEnglish

Related product manuals