EasyManuals Logo

Honeywell Temaline TK-S014 User Manual

Honeywell Temaline TK-S014
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
TK_S014 Installation Manual
19
For complete system details on this topic please refer: Temaline - installation in Harsh Environment
whitepaper
General rules
In case of installation of the device in harsh environment apply the following rules:
All the cables must run into an isolated and dedicated track;
The cables must not run parallel to high voltage cables ( > 50Vac).
Distance from high electromagnetic source must be > 10mt (an Electromagnetic source is a device
that generates high electromagnetic noise at frequency from 150Kz to 1 Ghz (tested up to 10V/m
(61000-4-6)) or Power frequency magnetic noise (tested up to 100V/m (61000-4-8)).
Cables rules
INPUT cables (door side) shielded to local Earth ground (Shield type: braid shield 90% coverage)
OUT Cables (door side) shielded to local Earth ground (Shield type: braid shield 90% coverage)
POWER SUPPLY cables connected to RTUQs or other PWS - unshielded
LON cable unshielded twisted pair
WEIGAND cable (reader side) - shielded to local Earth ground length max 3mt (Shield type: braid
shield 90% coverage)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Temaline TK-S014 and is the answer not in the manual?

Honeywell Temaline TK-S014 Specifications

General IconGeneral
BrandHoneywell
ModelTemaline TK-S014
CategoryControl Unit
LanguageEnglish

Related product manuals