Honeywell TH8320WF - Wiring; Terminal Designations

Honeywell TH8320WF
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
69-2733EFS—01 2
Y2
W2
K
S1
S2
RC
R
W
Y
G
C
RC
R
O/B
Y
G
C
R
W
G
C
Y
HEAT PUMP
CONVENTIONAL
Y2
L
E/AUX
K
S1
S2
MCR34051
Conventional Terminal Letters:
Y2 2nd stage compressor contactor.
W2 2nd stage heat relay.
K Optional wirer save module.
S1 Optional outdoor or remote sensor.
S2 Optional outdoor or remote sensor.
Rc Cooling power. Connect to secondary side
of cooling system transformer.
R Heating power. Connect to secondary side
of heating system transformer.
W 1st stage heat relay.
Y 1st stage compressor contactor.
G Fan relay.
C Common wire from secondary side of
cooling transformer (if 2 transformers).
Heat Pump Terminal Letters:
Y2 2nd stage compressor contactor.
L Heat pump reset (powered continuously
when System is set to Em Heat; system
monitor when set to Heat, Cool or Off).
E/Aux Auxiliary/Emergency heat relay.
K Optional wirer save module.
S1 Optional outdoor or remote sensor.
S2 Optional outdoor or remote sensor.
Rc Cooling power. Connect to secondary side
of cooling system transformer.
R Heating power. Connect to secondary side
of heating system transformer.
O/B Changeover valve for heat pumps.
Y 1st stage compressor contactor.
G Fan relay.
C Common wire from secondary side of
cooling system transformer.
Terminal Designations
Wiring

Other manuals for Honeywell TH8320WF