5 69-2733EFS—01
System setup
Function Settings & Options
0300
Manual/Auto
Changeover
0 Manual changeover (Heat/Cool/Off).
1 Automatic changeover (Heat/Cool/Auto/Off). Automatically turns on Heat
or Cool based on room temperature. Note: System maintains minimum
3°F difference between heat and cool settings.
0310
Auto changeover
deadband
3 Heat/cool temperature 3°F apart (1.5°C)
[Other options: 2-9 (2°F to 9°F/1°C to 5°C)])
0320
Temperature For-
mat (°F/°C)
0 Fahrenheit
1 Celsius
0330
Automatic Daylight
Saving Time Ad-
justment
0 Off
1 On
0340
Remote Temp
Sensor
0 None
1 Outdoor for Display
2 Outdoor for Control
3 Remote Indoor
0346
Dual Fuel Heat
Pump Upstage to
Furnace Timer
0 Disabled
1 30 minutes
3 60 minutes
5 1.5 hours
6 2 hours
7 3 hours
8 4 hours
9 5 hours
10 6 hours
11 8 hours
12 10 hours
13 12 hours
14 14 hours
15 16 hours
0347
Droop Temperature
(Steady State)
2 °F (1.0 °C)
[Other options: displayed in °F or °C]
0349
Backup Heat
Manual Droop Tem-
perature
0 Comfort (Off)
1 Economy
0350
Heat Pump Com-
pressor Lockout
0 Off
[Other options: displayed in °F or °C]
0360
Heat Pump Aux
Lockout
0 None
[Other options: displayed in °F or °C]
0500
Filter Change
Reminder
The reminder
appears after
selected number of
days run time not
actual time.
0 Off (no reminder)
1 Reminder after 10-day run time (about 1 calendar month)
2 Reminder after 30-day run time (about 3 calendar months)
3 Reminder after 60-day run time (about 6 calendar months)
4 Reminder after 90-day run time (about 9 calendar months)
5 Reminder after 120-day run time (about 1 calendar year)
6 Reminder after 180-day run time (about 18 calendar months)
7 Reminder after 270-day run time (about 2 calendar years)
8 Reminder after 365-day run time (about 3 calendar years)
0502
Furnace lter
for Run time
0 Counts both heat and cool
1 Counts cool only
0510
Humidier Pad
Replacement Re-
minder
0 Disabled
1 30-day run time (about 3 months)
2 60-day run time (about 6 months)
3 90-day run time (about 9 months)
0520
UV Lamp Replace-
ment Reminder
0 Disabled
1 365 days
2 730 days