• For mounting on a ush wallbox of depth greater than 25mm.
• Wiring to terminals must be done before wallplate is screwed to wallbox.
• Product requires a permanent 230Vac mains power supply to operate
• Switch output is potential-free 24V … 230Vac
• Installation should be carried out by a competent person.
• All wiring must be in accordance with IEE regulations.
• This unit is for xed wiring only.
• A switch, having contact separation of at least 3mm in all poles must be incorporated in the
xed wiring as a means of disconnecting the supply.
• The system must be appropriately fused. A fuse rating of no more than 5Amps should be installed.
• The unit is Class II (double insulated ) so device earthing is not required. A hook is provided for
parking an earth wire.
Installation notes read these prior to installation