V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES
60-2133—10 4
a
96 in. (2438 mm) leads also available.
b
Includes integral changeover Aquastat
®
control.
c
Valve available with reduced (2.5 Cv [2.1 kv]) rating on bypass
port. Sweat fitting only.
Table 1.
Powerhead Valve Body
Model
Power Required
Type of Wire Hookup
Line Fittings
Flow Capacity
Rating
Valve Body
Pattern
De-energized
Position
Voltage
(Vac)
Freq
(Hz)
Type
Size
(in.) Cv kv
V4043A 100 50 / 60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Flare 1/2 3.5 3.0 Straight-
through
Normally
Closed
120 60 Sweat or Flare 1/2 1.0 or 3.5 .86 or 3.0
120 60 Sweat 3/4 8.0 6.9
208 60 Flare 1/2 3.5 3.0
220 50 Sweat or Flare 1/2 3.5 3.0
220 50 Flare 1/2 2.5 2.1
240 50 or 60 Sweat or Flare 1/2 3.5 3.0
V4043B
120
a
60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Sweat or Flare 1/2 3.5 3.0 Straight-
through
Normally Open
208 60 Sweat
220 50 Sweat or Flare
240 60 Sweat
277 60 Sweat
V4043E
(steam
only)
120 60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Sweat 1/2 Cv not Applicable
(15 psi [103 kPa]
pressure rating)
Straight-
through
Normally
Closed
V4044A 100 50 / 60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Flare 1/2 4.0 3.4 2-Position
Diverting
Port A Normally
Closed
120
a
60 Sweat or Flare 1/2
4.0
c
3.4
208 60 Sweat 1/2 4.0 3.4
220 50 Sweat or Flare 1/2 4.0 3.4
240
50 or 60 Sweat or Flare 1/2 4.0 3.4
277 60 Sweat 1/2 4.0 3.4
120 60 Sweat 3/4 7.0 6.0
240 60 Sweat 3/4 4.0 3.4
V4044B
b
(bottom
inlet)
120 60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Sweat or Flare 1/2 3.5 3.0 2-Position
Diverting
Port A Normally
Closed
220 50 Sweat or Flare 1/2 3.5 3.0
120 60 Sweat 3/4 7.0 6.0
V8043A 24 50 / 60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Sweat or Flare 1/2 1.0 or 3.5 .86 or 3.0 Straight-
through
Normally
Closed
Sweat 3/4 3.5 3.0
Sweat 1
Inverted Flare 3/8 3.5 3.0
V8043B 24 50 / 60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Sweat or Flare 1/2 3.5 3.0 Straight-
through
Normally Open
Sweat 3/4
V8043E 24 50 / 60 18 in. (457 mm)
Leadwires and End
Switch,
1/2 in. conduit opening
Sweat 1/2 3.5 3.0 Straight-
through
Normally
Closed
Sweat 3/4 3.5 or 8.0 3.0 or 6.9
Sweat 1
Inverted Flare 3/8 3.5 3.0
V8043F 24 50 / 60 Terminal Board and End
Switch
Sweat 1/2 3.5 3.0 Straight-
through
Normally
Closed
Sweat 3/4
Sweat 1
Sweat 3/4 8.0 6.9
Sweat 1
V8043J
(steam)
24 50 / 60 18 in. (457 mm) Sweat 1/2 Cv not Applicable
(15 psi [103 kPa]
pressure rating)
Straight-
through
Normally Open
V8044A 24 50 / 60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Sweat or Flare 1/2
4.0
c
3.4 2-Position
Diverting
Port A Normally
Closed
Sweat 3/4 7.0 6.0
V8044B
b
24 50 / 60 18 in. (457 mm)
Leadwires,
1/2 in. conduit opening
Sweat 1/2 4.0 3.4 2-Position
Diverting
Port A Normally
Closed
V8044E 24 50 / 60 18 in. (457 mm)
Leadwires and End
Switch,
1/2 in. conduit opening
Sweat 1/2 4.0 3.4 2-Position
Diverting
Port A Normally
Closed
3/4 8.0 6.9