V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED VALVES
19 60-2133—10
OPERATION AND CHECKOUT
On 24 V systems, never jumper the valve coil 
terminals even temporarily. This may burn out the 
heat anticipator in the thermostat.
Operation
AUTOMATIC OPERATION
On a call for heat by the zone thermostat, the valve opens and 
its auxiliary switch contacts make, closing the circuit to the 
system circulator. In a multizone system with all the valve 
auxiliary switches wired in parallel, any zone calling for heat 
can operate the circulator. When the call for heat ends, the 
valve closes by integral spring return. The auxiliary switch 
contacts break the circulator circuit. 
MANUAL OPERATION
The motorized valve can be opened manually by lifting the 
manual opening lever over the stop and pushing slowly and 
firmly to the MAN. OPEN position. The stop permits the valve 
to be locked in the open position. The valve returns to 
automatic position when the valve is energized. 
NORMALLY CLOSED MODELS
With the manual opener set to AUTO and the powerhead 
energized, the valve is opened as shown in Fig. 36A. When the 
powerhead is de-energized, a spring-return mechanism drives 
the valve to the closed position as shown in Fig. 36B. The 
valve can also be opened with no electrical power by moving 
the manual opening lever over the stop and pushing slowly and 
firmly to the MAN. OPEN position. The stop permits the valve 
to be locked in the open position. The valve returns to the 
automatic position when the valve is energized. 
Auxiliary switch is not energized when the valve is manually 
opened. 
NORMALLY OPEN MODELS
When the powerhead is de-energized, a spring-return 
mechanism drives the valve to the open position (Fig. 36A). 
When energized, the valve is closed as shown in Fig. 36B. A 
reverse-acting thermostat is required to control a normally 
open valve.
NOTE: Inlet Port is stamped “A”, Outlet Port is stamped “B” 
on the valve body.
Fig. 36. V8043 operation for normally closed valve.
Checkout
1. Raise the setpoint on the zone thermostat above the 
room temperature to initiate a call for heat. 
2. Observe all control devices-the valve should open and 
the auxiliary switch should make the circuit to the circula-
tor or other valve at the end of the opening stroke. 
3. Lower the setpoint on the zone thermostat below the 
room temperature. 
4. Observe the control devices. The valve should close and 
the auxiliary equipment should stop. 
Service
This valve should be serviced by a trained, experienced 
service technician. 
1. If the valve is leaking, drain the system and check to see 
if the O-ring needs replacing. 
2. If the gear train is damaged, replace the entire power-
head assembly. See the Installation section. If the motor 
is burned out, replace the motor. See Replacement Parts 
list in the TRADELINE® Catalog. 
NOTE: Honeywell zone valves are designed and tested for 
silent operation in properly designed and installed 
systems; however, water noises can occur as a result 
of excessive water velocity or piping noises can occur 
in high temperature (higher than 212° F [100° C]) sys-
tems with insufficient water pressure. Valves are 
designed for normal cycling operations. Product life 
will be shortened if energized continuously. 
NOTE: These hydronic valves are not suitable for use in open 
loop systems where there is air exposure.
B
OUT
OPEN POSITION
A
A
IN
B
OUT
CLOSED POSITION
B
A
IN
M5951