V8200A,C,H,M AND VR8200A,C,H,M CONTINUOUS PILOT COMBINATION GAS CONTROLS
69-0422—03 2
INSTALLATION
When Installing This Product...
1. Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.
2. Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
Fire or Explosion Hazard can cause property 
damage, severe-injury or death.
Follow these warnings exactly:
1. Disconnect power supply before wiring to 
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas, 
turn off gas supply at the appliance service 
valve before starting installation, and perform 
Gas Leak Test after completion of installation.
3. Do not attempt to use a control set for natural 
(manufactured) gas on LP gas, or a control set 
for LP on natural (manufactured) gas.
4. Do not bend pilot tubing at control or pilot after 
compression nut has been tightened, or gas 
leakage at the connection may result.
5. Always install sediment trap in gas supply line 
to prevent contamination of gas control.
6. Do not force the gas control knob. Use only 
your hand to push down the reset button or turn 
the gas control knob. Never use any tools. If the 
knob or reset button will not operate by hand, 
the control should be replaced by a qualified 
service technician. Force or attempted repair 
may result in fire or explosion.
Never apply a jumper across or short the valve 
coil terminals. This may burn out the heat 
anticipator in the thermostat.
IMPORTANT
These gas controls are shipped with protective 
seals over inlet and outlet tappings. Do not 
remove seals until ready to connect piping.
Follow the appliance manufacturer’s instructions if 
available; otherwise, use the instructions provided below 
as a guide.
Convert between Natural and LP 
Gas
Fire or Explosion Hazard can cause property 
damage, severe-injury or death.
Do not attempt to use a control set for natural 
(manufactured) gas on LP gas, or a control set 
for LP on natural (manufactured) gas.
To convert a control from natural gas to LP gas, or from 
LP gas to natural gas, contact your Honeywell
®
 
representative.
Install Adapters to Control
If adapters are to be installed on the gas control, mount 
them as follows:
Flanges:
1. Choose the appropriate flanges for your application.
NOTE: A right angle inlet flange cannot be used with 
ECO connected.
2. Remove seal over control inlet or outlet.
3. Check to ensure that the O-ring is fitted in the 
groove of flange. If the O-ring is not attached or is 
missing, do not use the flange.
4. With O-ring facing valve, line up the screw holes on 
the control with the holes in the flange. Insert and 
tighten the screws provided with the flange (See 
Fig. 1). Tighten the screws to 25 in.-lbs 
(2.8 N·m) of torque to provide a gas-tight seal.
Bushings:
1. Remove seal over control inlet and outlet.
2. Apply moderate amount of good quality pipe 
compound to bushing, leaving two end threads 
bare. On LP installation, use compound resistant to 
LP gas. Do NOT use Teflon™ tape.
3. Insert bushing in control and thread pipe carefully 
into bushing until tight.
Fig. 1. Fasten Flange to Valve with 25 in.- lbs
(2.8 N·m) Torque.
M2913A
9/64 INCH HEX SCREWS (4) 
GAS CONTROL OUTLET
FLANGE
1
1
DO NOT OVERTIGHTEN SCREWS.
TIGHTEN TO 25 INCH-POUNDS.