x
Program feature or option
Permitted in
UL864? Y/N
Possible settings
Settings permitted in UL 864
27 TEST REPORT
INTERVAL
Y
Enter 0001-9999 for the test
report interval in hours.
Enter 0000 for test reporting.
Must be set to 0024
(Maximum 24 hours)
28 POWERUP IN
PREVIOUS STATE
Y
0 = disable
1 = enable
Must be set to 1 (enable).
37 DOWNLOAD
COMMAND ENABLES
N
0 = disable
1 = enable
Must be set to 0 for all
entries (disable).
41 NORMALLY
CLOSED OR EOLR
(ZONES 3-8)
N
0 = EOLR supervision
1 = N.C. loops
Must be set to 0 (EOLR
Supervision).
42 DIAL TONE PAUSE
Y
Enter the wait time for dial
tone detection:
0 = 5 seconds; 1 = 11 seconds;
2 = 30 seconds.
Must be set to 0 (5 seconds).
44 RING DETECTION
COUNT
N
Enter 00 to disable ring
detection.
Enter 01-14 for ring counts of
1-14.
Enter 15 to select Answering
Machine Defeat Mode
Must be set to 00 (disable).
54 UNATTENDED
MODE
N
0 = disable
1 = enable
Must be set to 0 (disable).
56 DYNAMIC
SIGNALING DELAY
Y
Enter 00-15 times 15 seconds.
Must be set to 6 (90
seconds).
77 AUTO TROUBLE
RESTORE
Y
0 = disable
1 = enable
Must be set to 1 (enable).
80 ZONE TYPE
RESTORES FOR TYPES
9, 10 & 14
N
0 = disable
1 = enable
Must be set to 1 (enable) for
zone type 9.
1
12 PROGRAM
NOTIFICATION SIGNAL
Y
0 = no
1 = yes
Must be set to 1 (yes).
1
13 SYSTEM SENSOR
REVERSING RELAY
N 0=use neither Zone 1 or Zone
2 inputs
1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2
inputs.
Not Used. Must be set to 0.
1
18 AFFECTS LOBBY
N
0 = disable
1 = enable
Must be set to 0 (disabled)
for partition 1.
1
19 ARMS LOBBY
N
0 = disable
1 = enable
Must be set to 0 (disabled)
for partition 1.
1
22 thru
1
25 CROSS-
ZONING PAIRS (1 4)
N
Enter 001-128
Enter 000,000 to disable
Must be set to 000,000
(disabled) for fire zones.
1
28 RF TRANSMITTER
LOW BATTERY SOUND
N
0 = disarmed state only
1 = both armed and disarmed
states
Must be set to 1 (both
armed and disarmed states).
1
29 RF TRANSMITTER
LOW BATTERY
REPORTING
N
0 = disable
1 = enable
Must be set to 1 (enable).

Table of Contents