xi
Program feature or option
Permitted in
UL864? Y/N
Possible settings
Settings permitted in UL 864
1
30 RF RECEIVER
SUPERVISION CHECK-
IN INTERVAL
N
Enter 0215 times 2 hours (4
30 hours)
Enter 00 to disable receiver
supervision
Maximum is 02 (4 hours) for
fire installations.
1
31 RF TRANSMITTER
CHECK-IN INTERVAL
N
Enter 0215 times 2 hours (4
30 hours)
Enter 00 to disable
transmitter supervision
Maximum is 02 (4 hours) for
fire installations.
1
35 ACCESS CONTROL
DIALER ENABLES
N 0 = disable
1 = enable
Not used. Must be set to 0.
1
44 WIRELESS
KEYPAD TAMPER
DETECT
N 0 = disable
1 = enable
Not used. Must be set to 0.
1
45 EXIT DELAY
SOUNDING (PARTITION
SPECIFIC)
N
0 = disable
1 = enable
Must be set to 0 (disable)
for partition 1.
1
48 WIRELESS
KEYPAD ASSIGNMENT
N 0 = none
1-8 = partition number
Not used. Must be set to 0.
1
49 SUPPRESS TX
SUPERVISION SOUND
N
0 = disable
1 = enable
Must be set to 0 (disable).
1
53 DISABLE
DOWNLOAD CALLBACK
N
0 = callback required
1 = no callback required
Must be set to 0 (callback
required).
1
57 5800 RF BUTTON
GLOBAL ARM
N
0 = disable
1 = enable
Must be set to 0 (disable).
1
58 5800 RF BUTTON
FORCE ARM
N
0 = disable
1 = enable
Must be set to 0 (disable).
1
60 ZONE 5 AUDIO
ALARM VERIFICATION
N
0 = disable
1 = enable
Must be set to 0 (disable).
1
69 PRINTER TYPE
N 0 = parallel printer
1 = serial printer
Not used.
1
72 EVENT LOG
PRINTER ONLINE
N 0 = disable
1 = enable
Not used. Must be set to 0.
1
73 PRINTER BAUD
RATE
N 0 = 1200
1 = 300
Not used.
1
76 CONTROL RELAY
(PART-SPECIFIC)
N
01-96 = relay number
00 = relay not used.
Must be set to 00 (relay not
used) for partition 1.
1
78 EXTENDED HOME
CONT EVENTS
N 1 = extended
0 = limited
Not used. Must be set to 0.
1
79 HOME CONTROL
EVENTS
N 0 = disable
1 = enable
Not used. Must be set to 0
in each entry.
2
07 AUTO-DISARM
DELAY (PART
SPECIFIC)
N
00 = no delay.
01-14 times 4 minutes (04-56)
delay.
15 = no auto disarming.
Must be set to 15 (no auto
disarming) for partition 1.
2
18 ENABLE GOTO
FOR THIS PARTITION
(partition-specific)
N
0 = disable
1 = enable
Must be set to 0 (disable)
for partition 1.