1-1
SECTION 1
General Description
••••••••••••••••••••••••••••••••••••••••••••••••
About the VISTA-128FBPN
The VISTA-128FBPN is an 8-partition, UL Listed commercial fire and burglary control panel with the following
features:
Up to 128 zones (hardwired, polling loop, and wireless zones)
Up to 150 user codes
Supervision of Notification Appliance Circuits, phone lines, keypads, RF receivers, and output devices
Scheduling capabilities (allows certain operations to be automated)
ULC
Scheduling is currently not approved for ULC applications.
The VISTA-128FBPN can interface with the following devices:
An ECP Communications Device that can send Contact ID messages
Features
Hardwire and Optional Expansion Zones
Provides 8 hardwire zones.
Supports up to 16 2-wire smoke detectors each on zone 1 and zone 2 (32 total).
Automatically resets 4-wire smoke detectors if the Aux Relay is programmed for smoke reset (3*61 = 2).
Supports up to 50 2-wire latching glassbreak detectors on zone 8.
Supports up to 119 additional expansion zones using a built-in polling (V-Plex) loop.
Supports up to 128 wireless zones, fewer if using hardwire and/or polling loop zones.
Can program burglary zones as silent in the alarm condition (alarm output is silent and the keypad does not display
or sound the alarm).
Provides three keypad panic keys: 1 + (A), + # (B), and 3 + # (C).
Full Status (Remote Interactive Service)
Peripherals Devices
Supports up to 31 addressable devices, (keypads, RF receivers, relay modules, etc.).
Supervises devices (keypads, RF receivers, and relay modules) and individual relays (up to 32), as well as system
zones (RF receivers and keypad panics).
Provides 96 outputs using 4204 and 4204CF Relay Modules, and V-Plex Relay Modules can activate outputs in
response to system events (alarm condition), at a specific time of day, at random times, and manually using the #70
Relay Command Mode.
Supports one additional style-Y supervised Notification Appliance Circuit using a 4204CF.
Supports the ADEMCO 4146 Keyswitch on any one of the system's eight partitions.
Can be used with Commercial Fire Listed 24VDC Power Supplies.
Arming/Disarming and Bypassing
Can arm the system with zones faulted (Vent Zone). These zones are automatically bypassed and can be
programmed to automatically unbypass when the zone restores.
Can arm with entry/exit and interior type zones faulted (Arm w/Fault). These zones must be restored before the exit
delay expires, otherwise an alarm is generated.
U
L
Vent zones cannot be used in UL installations.
You must disable the Force Arm option (used in conjunction with the Arm w/Fault option), in UL installations.