xiv
Item Feature Range Shipping
Default
SIA Requirement*
1*61 Abort Verify 0 = Disable
1 = Enable
Enabled Enabled
Zone
Programming
Auto Stay
Zone, Zone
type 04 has
this feature
enabled by
default
Auto Stay Arm or
Occupied Premises
0 = Disable
1 = Enable
1 (Enabled) Enabled
Zone
Programming
(Abort
Window
Enable)
Abort Window (for
non-fire zones)
0 = no abort window
1 = yes, use abort
window according to *88
selection
1 = yes Yes (all non-fire zones)
Zone
Programming
(Swinger
Suppression
Enable)
Swinger Suppression
Enable
0 = no suppression
1 = yes, suppress alarms
according to *84
selection
Yes (enabled) Yes (enabled (all zones))
Zone
Programming
Tamper
Option
Fire Alarm
Verification
For Zone Response
Type 16 (Fire) tamper
selection must be set to
“0”
Disabled Enabled unless sensors
can self verify
- Exit Time and
Progress
Annunciation/Disable
for Remote Arm (Not
Evaluated for SIA
CP-01)
Always Enabled Enabled Enabled
- Cancel Window 5 minutes Enabled Not required to be
programmable
- Cancel Annunciation
- Keypad displays
“Alarm Cancel” when
report is received
NA Enabled Enabled
- Programmable Cross
Zoning Time
Both zones must be
faulted within 5 minutes
Per
Manufacturer
Per walk path in protected
premises
User
Authority
Level 6
Duress Feature NA Disabled Disabled
* Programming at installation may be subordinate to other UL requirements for the intended application.
** In accordance with UL standards, the combined Entry Delay time and Abort Window cannot exceed 1
minute.