xiii
Program feature or option
Permitted in
UL864? Y/N
Possible settings
Settings permitted in UL 864
3
60 BELL 2 & AUX
RELAY TIMEOUT
Y
Enter 01-15 multiplied by 2
minutes.
00 = no timeout.
Must be set to “3” (Minimum
of 6 minutes).
3
82 ENABLE
BURGLARY FEATURES
ON PARTITION 1
N
0 = disable
1 = enable
Must be set to “0” (disable).
RESTRICTION FOR FIRE
RELAYS
Y
Yes
No
Restriction for # 70 must be
set to Yes when
programming fire relays.
NOTE: When there is a conflict between UL864 and CP-01, UL864 will take precedence.
SIA CP-01 Quick Reference Chart
The minimum required system for SIA CP-01 is a UL Listed Control, Keypad and Bell.
Item Feature Range Shipping
Default
SIA Requirement*
*09 Entry Delay # 1 02 – 15 multiplied by 15
seconds
00 = 240 sec (4 minutes)
30 Seconds` At least 30 Seconds **
*10 Exit Delay #1 03 – 15 multiplied by 15
seconds
60 Seconds 60 Seconds
*11 Entry Delay # 2 02 – 15 multiplied by 15
seconds
00 = 240 sec (4 minutes)
30 Seconds At least 30 Seconds **
*12 Exit Delay #2 03 – 15 multiplied by 15
seconds
60 Seconds 60 Seconds
*28 Power Up in
Previous State
0 = no
1 = yes
Yes Yes
*57 Dynamic Signaling
Priority
0 = primary dialer
1 = Communicator as
first reporting destination
0 (primary dialer) 0 (primary dialer)
*84 Swinger Suppression 01= 1 alarm
02= 2 alarms
1 alarm 1 alarm
*88 Abort Window Time
(for non-fire zones)
1 = 15 seconds
2 = 30 seconds
3 = 45 seconds
30 Seconds At least 15 Seconds **
1*21 Exit Time Reset 0=no
1=Resets Exit Delay to
programmed value after
zone is closed and then
faulted prior to end of exit
delay.
1 (Enabled) 1 (Enabled)
1*22 – 1*25 Cross Zoning Zone 001 – 128
000, 000 = Disabled
Disabled Enabled and two (or
more) zones programmed
1*42 Call Waiting Defeat 0 = no
1 = yes
Disabled (0) Enabled if user has call
waiting