– 21 –
Expert Mode Zone Programming
Expert mode allows you to program zones using the minimum number of screens and keystrokes.
Enter the Programming mode with [Installer Code] + 8 0 0
Before programming your zones, do the following:
1. Program field 2✱00: Number of Partitions.
2. Enable your RF Receiver in
Device Programming
menu mode.
To program your zones, press ✱93 to display the "ZONE PROG?" prompt. Enter “0” (NO) to each prompt until the “EXPERT
MODE?” prompt appears.
PROMPT
EXPLANATION
EXPERT MODE?
1 = YES 0 = NO 0
Press 1 to enter Expert mode.
SET TO CONFIRM?
0 = NO 1 = YES 0
This prompt appears once upon entering Expert Mode.
If you select “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have
been entered later.
Zn ZT P RC In L
001 03 1 10 HW
-
A summary display appears, showing zone 1’s current programming or default values.
Zn ZT P RC In L
010 03 1 10 RF 1s
Enter the desired 3-digit zone number and press [✱].
NOTE: If you want to exit the Expert mode, enter “000” + [✱].
If an “s” appears after the loop number, it indicates that the transmitter’s serial number has been enrolled.
Use the [D] key to enter and duplicate wireless keys (see “Entering Wireless Keys” later)
Zn ZT P RC In L
010 03 1 10 RF
-
Enter all zone information except for Loop number, or press “C” to copy the zone information on this screen
from the last saved zone (including Loop).
ZT = Zone Type
P = Partition
RC = Report Code
In = Input Device Type
L = Loop number to which the sensor is connected.
NOTE: Pressing the [C] copies the zone information from the last saved zone, which includes the
input type. Verify this information is correct for this zone.
On this screen:
• Use the [A] key to move to the right.
• Use the [B] key to move to left and to back up to “ZT” field.
Press [✱] to accept the existing or newly-entered zone information.
ZN B M V A C E AD
010 2 1 1 0 1 1 01
Enter the remainder of the zone’s information, or press the [C] key to copy the zone attributes on this screen
from the last saved zone.
B = Bell/Relay Assignment
M = Maintenance (only used if “In” = 3 or 6)
V = Do Not Use. Must be set to “0”.
AC = Access Point (only used if In = 6)
E = Do Not Use. Must be set to “0”.
AD = Address (only used if “In” = 9)
If “In” = 9, enter the Device Address
NOTE: Pressing the [C] copies the zone attributes from the last saved zone. Verify the attributes for
this zone are correct.
On this screen:
• Use the [A] key to move to the right.
• Use the [B] key to move to left and to back up to “V” field.
Press [✱] to accept existing information.