– 8 –
VISTA-32FB Programming Form
Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,
see the
Partition-Specific Fields
section for programming these fields. Standard default (*97) values are shown in brackets [ ];
otherwise, default = 0.
*00 INSTALLER CODE | | |
Enter 4 digits, 0-9 [5140]
*08 TEMPORAL SIREN PULSE - Not Used at this time.
*09 ENTRY DELAY #1 [02] |
00, 02-15 times 15 seconds
Maximum "03" for Commercial Burglary installations.
*10 EXIT DELAY #1 [03] |
00, 03-15 times 15 seconds
Maximum "04" for Commercial Burglary installations.
*11 ENTRY DELAY #2 [06] |
00, 02-15 times 15 seconds (must be longer than Entry Delay
#1). Maximum "03" for Commercial Burglary installations.
*12 EXIT DELAY #2 [08] |
00, 03-15 times 15 seconds (must be longer than Exit Delay
#1). Maximum "04" for Commercial Burglary installations.
*13 BELL 1 TIMEOUT [03] |
01-15 times 2 minutes. Must be minimum 16 minutes for
Commercial Burglary installations. Must be minimum 6
minutes for Commercial Fire installations.
*15
KEYSWITCH ASSIGNMENT [0]
Enter partition in which keyswitch used, 1-2; 9=silences
Notification Appliance Circuit if fire present; 0=disable
*16 BELL 1 CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable.
NOTE: If using a keyfob, when the button is pressed, either for
arming or disarming, the bell will ding indicating that the button
is working.
Must be "1" for Commercial Burglary installations.
*17 AC LOSS KEYPAD SOUNDING [1]
1=enable; 0=disable
Must be "1" for Commercial Fire installations.
*19 RANDOMIZE AC LOSS REPORT [2]
0= within 2 minutes; 1=10-40 min; 2=1-3 hours; 3=6-12 hours
without Type 13, 1-3 hours with Type 13.
*20 VIP MODULE PHONE CODE - Not used.
| |
Enter 01 - 09 for the first digit; enter [00], [11]
11 for “*” or 12 for “#” for the second digit.
Must be set to "00" for Commercial Burglary and Commercial
Fire installations.
*22 KEYPAD PANIC ENABLES [001]
1=enable; 0=disable 995 996 999
NOTE: Use for burglary panic types only. Do not use in
partition 1 in Fire systems.
*23 MULTIPLE ALARMS [1]
1=enable; 0=disable
Must be “1” for Commercial Burglary installations
*24 IGNORE EXPANSION ZONE TAMPER [0]
1=Ignore; 0=Enable tamper for RF and V-Plex.
Must be "0" for Commercial Burglary and Commercial Fire
installations if using these devices.
*25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
1=enable; 0=disable
*26 INTELLIGENT TEST REPORTING [0]
1=enable (no report sent if any other report was recently sent);
0=disable (send report at programmed interval, field *27)
Must be “0” for Commercial Burglary and Commercial Fire
installations.
*27 TEST REPORT INTERVAL [0024] | | |
Enter interval in hours, 0001-9999; 0000=no report;
Max. 0024 for Commercial Burglary and Commercial Fire
installations.
*28 POWER UP IN PREVIOUS STATE [1]
1=enable; 0=disable
Must be “1” for Commercial Burglary and Commercial Fire
installations.
*29 QUICK ARM [1]
1=enable; 0=disable
*30 MAIN DIALER TOUCHTONE OR ROTARY [1]
1=TouchTone; 0=rotary
*31 PABX ACCESS CODE | | | |
00-09; B-F (11-15)
*32 PRIM. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*33
PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2-second pause
*34
SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2-second pause