– 26 –
PROMPT
EXPLANATION
Enter the rest of the codes in the same manner. Other codes in System Group #3 are:
Early Close
Late Open
Late Close
Failed to Open
Failed to Close
Auto-Arm Failed
Schedule Change
Once you have entered these report codes, the system prompts you with the Quit menu.
QUIT REPORT MENU
1 = YES 0 = NO 0
If you have completely finished entering report codes, press [1] (Y) to quit
Report Code Programming
. If you
wish to enter other system report codes, enter 0 (N)
Press [] to continue.
System Group #4 Codes
PROMPT
EXPLANATION
SYSTEM GROUP #4 ?
1 = YES 0 = NO 0
To enter System Group #4 codes, press [1] (YES).
WALK TEST START
1st 00 2nd 00
Enter the first digit of the Fire Walk Test Start Report Code. Press []. Enter the second digit of the report
code.
Press [] to continue.
Enter the rest of the codes in the same manner. Other codes in System Group #4 are:
Fire Walk-Test End.
Off-Normal.
Once you have entered these report codes, the system prompts you with the Quit menu.
QUIT MENU MODE?
1 = YES 0 = NO 0
Enter 1 to exit back to normal Programming mode. Enter 0 to stay in Menu mode.