–3–
Program feature or option
Permitted in
UL864? Y/N
Possible settings Settings permitted in UL 864
80 ZONE TYPE RESTORES
FOR TYPES 9, 10 & 14
N 0 = disable
1 = enable
Must be set to “1” (enable) for zone
type 9.
1
12 PROGRAM
NOTIFICATION SIGNAL
Y 0 = no
1 = yes
Must be set to “1” (yes).
1
13 SYSTEM SENSOR
REVERSING RELAY
N
0=use neither Zone 1 or Zone 2 inputs
1=use Zone 1 input;
2=use Zone 2 input;
3=use Zone 1 and Zone 2 inputs.
Not Used. Must be set to “0”.
1
18 AFFECTS LOBBY
N 0 = disable
1 = enable
Must be set to “0” (disabled) for
partition 1.
1
19 ARMS LOBBY
N 0 = disable
1 = enable
Must be set to “0” (disabled) for
partition 1.
1
22thru
1
25 CROSS-ZONING
PAIRS (1 – 4)
N Enter 001-032
Enter 000,000 to disable
Must be set to “000,000” (disabled)
for fire zones.
1
28 RF TRANSMITTER LOW
BATTERY SOUND
N 0 = disarmed state only
1 = both armed and disarmed states
Must be set to “1” (both armed and
disarmed states).
1
29 RF TRANSMITTER LOW
BATTERY REPORTING
N 0 = disable
1 = enable
Must be set to “1” (enable).
1
30 RF RECEIVER
SUPERVISION CHECK-IN
INTERVAL
N Enter 02–15 times 2 hours (4–30
hours)
Enter 00 to disable receiver
supervision
Maximum is 02 (4 hours) for fire
installations.
1
31 RF TRANSMITTER
CHECK-IN INTERVAL
N Enter 02–15 times 2 hours (4–30
hours)
Enter 00 to disable transmitter
supervision
Maximum is 02 (4 hours) for fire
installations.
1
35 ACCESS CONTROL
DIALER ENABLES
N 0 = disable
1 = enable
Not used. Must be set to “0”.
1
44 WIRELESS KEYPAD
TAMPER DETECTION
N 0 = disable
1 = enable
Not used. Must be set to “0”.
1
45 EXIT DELAY SOUNDING
(PARTITION SPECIFIC)
N 0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
1
48 WIRELESS KEYPAD
ASSIGNMENT
N 0 = none
1-2 = partition number
Not used. Must be set to “0”.
1
49 SUPPRESS TX
SUPERVISION SOUND
N 0 = disable
1 = enable
Must be set to “0” (disable).
1
53 DISABLE DOWNLOAD
CALLBACK
N 0 = callback required
1 = no callback required
Must be set to “0” (callback
required).
1
57 5800 RF BUTTON
GLOBAL ARM
N 0 = disable
1 = enable
Must be set to “0” (disable).
1
58 5800 RF BUTTON FORCE
ARM
N 0 = disable
1 = enable
Must be set to “0” (disable).
1
60 ZONE 5 AUDIO ALARM
VERIFICATION
N 0 = disable
1 = enable
Must be set to “0” (disable).
1
72 EVENT LOG PRINTER
ONLINE
N 0 = disable
1 = enable
Not used. Must be set to “0”.
1
73 PRINTER BAUD RATE
N 0 = 1200
1 = 300
Not used.
1
76 CONTROL RELAY
(PART-SPECIFIC)
N 01-96 = relay number
00 = relay not used.
Must be set to “00” (relay not used)
for partition 1.
2
07 AUTO-DISARM DELAY
(PART SPECIFIC)
N 00 = no delay.
01-14 times 4 minutes (04-56) delay.
15 = no auto disarming.
Must be set to “15” (no auto
disarming) for partition 1.
2
18 ENABLE GOTO FOR
THIS PARTITION (partition-
specific)
N 0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2
21 SUPERVISION PULSES
FOR COMMUNICATIONS
DEVICE
N 0 = disable
1 = enable
Not used. Must be set to “00000”
(disable).
2
22 DISPLAY FIRE ALARMS
OF OTHER PARTITIONS
N 0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.
2
23 DISPLAY BURG, PANIC
AND CO ALARMS FOR OTHER
PARTITIONS
N 0 = disable
1 = enable
Must be set to “0” (disable) for
partition 1.