EXCEL 10 W7761A INPUT/OUTPUT DEVICE
13 74-2699
Supported Sensors: T7770A,B,C,D sensor—(current feature that can be used with the RIO Device) and T7780
DDWM.
Discharge Air Temperature:
Type: RTD.
Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050,
C7031K1017.
Outdoor Air Temperature:
Type: RTD.
Supported Sensors: C7170A1002.
Return Air Temperature:
Type: RTD.
Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050,
C7031K1017.
Mixed Air Temperature:
Type: RTD.
Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050,
C7031K1017.
*The PT3000 sensor is not recommended for floating control (real time - discharge or return configured as space sensor).
The PT3000 sensor is intended for monitoring or differential (staged) control.
Outdoor Air Humidity:
Type: Voltage/Current.
Supported Sensors: C7600B1000 and C7600B1018 (2 to 10V), C7600C1008 (4 to 20mA).
Return Air Humidity:
Type: Voltage/Current.
Supported Sensors: C7600B1000 and C7600B1018 (2 to 10V), C7600C1008 (4 to 20mA).
Outdoor Air Enthalpy:
Type: Current.
Supported Sensors: C7400A1004 (4 to 20mA).
Return Air Enthalpy:
Type: Current.
Supported Sensors: C7400A1004 (4 to 20mA).
Air Filter Differential Pressure:
Type: Voltage.
Supported Sensors: Third party 2 to 10V, 0 to 5 inw ( 0 to 1.25 kPa) differential pressure sensors.
Space CO
2
Sensor:
Type: Voltage.
Supported Sensors: Third party 0 to 10V, 0 to 2000 ppm CO
2
sensors.
Outdoor Air CO
2
Sensor:
Type: Voltage.
Supported Sensors: Third party 0 to 10V, 0 to 2000 ppm CO
2
sensors.
Outdoor Air CO Sensor:
Type: Current.
Supported Sensors: Third party 4 to 20mA, 0 to 300 ppm CO sensor.
Monitor Sensor for network use:
Type: Voltage.
Supported Sensors: Third party 2 to 10V, 2 to 10 volts displayed.
Digital Inputs:
Dry-contact inputs are sensed using a 9 milliamp at 4.8 volts detection circuit. It is very important that the device used contains
high quality, noncorroding contacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as
gold or silver) or pimpled or sealed contacts to assure consistent, long-term operation.
Triac Outputs:
Triac Outputs on the RIO:
Power ratings: 20 Vac to 30 Vac at 25 mA MIN to 500 mA MAX current for any voltage.