EasyManua.ls Logo

Honeywell W7761A - Table 7. W7761 A I;O Description

Honeywell W7761A
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
25 74-2699
3/8`
(10)
STRIP 3/8 IN. (10 MM) FROM WIRES `
TO BE ATTACHED AT ONE TERMINAL.
1. 2. TWIST WIRES TOGETHER `
WITH PLIERS (A MINIMUM `
OF THREE TURNS).
TWO 14 AWG`
(2.0 MM
2
) WIRES
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) `
BEFORE INSERTING INTO TERMINAL AND TIGHTENING`
SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS
`
TO CHECK FOR GOOD MECHANICAL CONNECTION.
M10086
Fig. 15. Attaching two or more wires at terminal blocks.
See Table 7 for a description of the W7761A terminals.
Table 7 . W7761A I/O Description.
Terminal
Terminal
Number Description
OUT 8 16 Digital Output 8
OUT 7 17 Digital Output 7
OUT 6 18 Digital Output 6
OUT 5 19 Digital Output 5
OUT 4 20 Digital Output 4
OUT 3 21 Digital Output 3
OUT 2 22 Digital Output 2
OUT 1 23 Digital Output 1
+24Vac (H) 25 Power for the device
COM (N) 24 Return for power to device
E-Bus 15 Echelon® communications screw terminals
E-Bus 14 Echelon® communications screw terminals
DI -4 31 Digital Input 4
DGND 30 Digital Ground
DI -3 29 Digital Input 3
DI -2 28 Digital Input 2
DGND 27 Digital Ground
DI -1 26 Digital Input 1
22 VDC out 13 22 Vdc power supply for auxiliary devices with a maximum current of 50 mA.
AI-6 12 Analog Input 6 voltage or current
AGND 11 Analog ground
AI-5 10 Analog Input 5 voltage or current
AI-4 9 Analog Input 4 resistance
AGND 8 Analog ground
AI -3 7 Analog Input 3 resistance
AI-2 6 Analog Input 2 resistance

Table of Contents