EXCEL 10 W7761A INPUT/OUTPUT DEVICE
53 74-2699
Table C1. Input/Output Points (Left Continued).
Engineering Units:
English (Metric) or
Digital
State
or
Value
of
User Address NvName Field Name States plus Range State Default
SrcDigIn2Sts nvoRemoteDigIn(1) DI2Value 0 to 255 0
nvoRemoteDigIn(1) DI2State Refer to the DI1State enumerated list
shown in the Eng. Units/States column.
ST_NUL
SrcDigIn3Sts nvoRemoteDigIn(2) DI3Value 0 to 255 0
nvoRemoteDigIn(2) DI3State Refer to the DI1State enumerated list
shown in the Eng. Units/States column.
ST_NUL
SrcDigIn4Sts nvoRemoteDigIn(3) DI4Value 0 to 255 0
nvoRemoteDigIn(3) DI4State Refer to the DI1State enumerated list
shown in the Eng. Units/States column.
ST_NUL
SrcHumidAI5 nvoRemoteHum(0) percent
-163 to 163
0
SrcHumidAI6 nvoRemoteHum(1) percent
-163 to 163
0
SrcPressAI5 nvoRemotePres(0) inw -131.5 to 131.5
kPa (-32.768 to 32.767)
0
SrcPressAI6 nvoRemotePres(1) inw -131.5 to 131.5
kPa (-32.768 to 32.767)
0
SrcTempAI1 nvoRemoteTemp(0) degrees F -40 to 240
degrees C (-40 to 116)
0
SrcTempAI2 nvoRemoteTemp(1) degrees F -40 to 240
degrees C (-40 to 116)
0
SrcTempAI3 nvoRemoteTemp(2) degrees F -40 to 240
degrees C (-40 to 116)
0
SrcTempAI4 nvoRemoteTemp(3) degrees F -40 to 240
degrees C (-40 to 116)
0
SrcVoltageAI nvoRemoteVolt Volts
0.0 to 10.5
0
)