Each terminal can accommodate the following 
gauges of wire: 
•  Single wire: from 22 AWG to 18 AWG solid or 
stranded 
•  Multiple wires: up to two 18 AWG stranded, 
with 1/4 watt wire-wound resistor 
 
Prepare wiring for the terminal blocks, as 
follows: 
•  Strip 
1
/
2
 in. (13 mm) insulation from the 
conductor. 
•  Cut a single wire to 
3
/
16
 in. (5 mm). Insert 
the wire in the required terminal location 
and tighten the screw. 
•  If two or more wires are being inserted into 
one terminal location, twist the wires 
together a minimum of three turns before 
inserting them (see Fig. 15). 
•  Cut the twisted end of the wires to 
3
/
16
 in. 
(5 mm) before inserting them into the 
terminal and tightening the screw. 
•  Pull on each wire in all terminals to check 
for good mechanical connection. 
 
 
COMMISSIONING 
Automatic MAC Addressing 
In contrast to other controllers the WEB-
VA423B24N controller features automatic MAC 
addressing. 
The MAC addresses which the individual WEB-
VA423B24N controllers in the BACnet MS/TP 
channel assign to themselves are not assigned in 
sequential order. 
Rather, they assign those numbers (MAC Address) 
in the range of 1 to maxMaster currently not in use 
by another device in the BACnet MS/TP channel 
(the MAC Address of "0" is reserved by default for 
the router / plant controller, itself). 
All WEB-VA423B24N controllers are BACnet 
MS/TP masters. Every master performs periodic 
polling for the possible appearance of new masters. 
Each master "knows" the identity of the "next" 
master (i.e., that WEB-VA423B24N controller with 
the next-highest MAC Address) on the BACnet 
MS/TP bus and to which it must therefore pass the 
token. The polling process includes a search for 
new masters which might have MAC addresses 
lying between its own MAC address and that of the 
"next" master. 
The property maxMaster specifies the highest-
allowable address for master nodes. The 
maxMaster is set to 35 by default, thus 
guaranteeing that, on a BACnet MS/TP bus with, 
for example, 35 WEB-VA423B24N controllers, all of 
the other WEB- VA423B24N controllers will be 
found. Both the property maxMaster and the 
property MAC address are writeable properties that 
can be changed. 
NOTE:  You should not attempt to program a MAC 
Address outside the range of 1 to 
maxMaster. 
 
 
Fig.  16. Automatic MAC addressing 
In the scenario depicted in Fig.  16, some of the 
controllers in the BACnet MS/TP channel do not 
feature automatic MAC addressing; rather, their 
MAC addresses were assigned manually (for 
example, using their two dip switches). Thus, when 
a new WEB- VA423B24N is added to the channel, 
when its automatic MAC addressing function is 
triggered, it will assign itself an available (i.e., 
unoccupied) MAC address.