XNX Universal Transmitter
Specications
142
EC Sensor Performance Data, Factory Mutual Verified
(see Certications by Part Number Series)
Gas
Cartridge
Part Number
Selectable Full
Scale Range (Dis-
play and 4-20mA
Full Scale)
Default
Range
Range
Incre-
ments
Lower
Alarm
Limit
Lower
Detection
Limit
Lower
Explosive
Limit
(% Vol)
Zero
Deviation
Selectable
Cal Gas
Range
Default
Cal Point
Response
Time T50
(sec)
Response
Time T90
(sec)
Accuracy
Operating Temperature Operating Humidity
EC Sensor
Expected
LIfe
(months)
Min Max Min Max
O
2
Oxygen XNXXSO1FM n/a 23.0% Vol n/a 5.0%Vol 5% Vol n/a n/a
20.9 %Vol
(fixed)
20.9 %Vol T20 <10 <30 <+/-0.5 %Vol -30°C / -34°F 55°C /131°F 15% RH 90% RH 24
H
2
S Hydrogen Sulfide XNXXSH1FM 10.0 to 50.0 ppm 15.0 ppm 0.1 ppm 5.0 ppm 1.5 ppm n/a -2.5 ppm
30 to 70%
of the
selected full
scale range
10 ppm <20 <30
2 ppm or 10% of
reading, whichever
is greater
-40°C / -40°F 55°C / 131°F 15% RH 90% RH 12
CO Carbon Monoxide XNXXSC1FM
1
100 to 1000 ppm 300 ppm 100 ppm 30 ppm 15 ppm na/ -25 ppm 100 ppm <15 <30 See footnote 1 -40°C / -40°F 55°C / 131°F 15% RH 90% RH TBD
Footnotes:
1. XNXXSC1FM accuracy over temperature <±10% of reading 20°C/68°F to 55°C/131°F, <±20% of reading 20°C/68°F to -10°C/14°F, <±30% of reading -10°C/14F to -20°C/-4°F.
Recalibration is recommended if the temperature of the local environment has varied by more than -30°C.
Notes:
Performance gures are measured by test units calibrated at 50% of full scale, at ambient conditions of 20°C, 50% RH, with the EC weatherproof cover attached
IP rating of FM Cartridges is IP63.
Barometric pressure effects on the O
2
sensor: The output from the O
2
sensor has pressure effects of <0.1% change of output per % change in pressure. When the barometric
pressure changes by ±20% the output from the O
2
sensor changes <±0.4%Vol. However, the oxygen sensor shows transient behavior when subjected to a rapid change in
ambient pressure due to either weather or altitude. For example, a 10KPa instantaneous positive pressure step change may cause an overscale alarm condition for a period
of about 12 seconds.
Operating the EC sensor at extended temperature ranges for a prolonged time period exceeding 12 hours my cause deterioration in the sensor performance and shorten
sensor life. Extended temperature range for XNX EC sensors is -40°C ot -20°C.
Response times may increase at lower temperatures.
FM performance verification is limited to the requirements of the standards identified in Table 6.3 for each cartridge.
Contact Honeywell Analytics for additional data or details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX-UTAI Series and is the answer not in the manual?

Honeywell XNX-UTAI Series Specifications

General IconGeneral
BrandHoneywell
ModelXNX-UTAI Series
CategoryTransmitter
LanguageEnglish

Related product manuals