3.5 Set Service
‘SET SERVICE’
PARAMETER
Parameter
ID
LoT™ Display
Description
Default
Value
Range of
Values
Description [LoT™ Display Description]
Enable or disable service
alarm feature
AL SERV MODE 0 0, 1 0 = disabled
1 = enabled
[DISABLED]
[ENABLED]
Number of days till next
Service
d SERV DAYS 364 001 to
400
001….400
000 = service is overdue
[SET DAY COUNT]
Number of days for
advance warning
Ad DAYS NOTICE 28 0 to 28 0 …28 [SET DAYS NOTICE]
Action taken at time-out to ACTION TYPE 2 0, 1, 2 0 = no action,
1 = switch off,
2 = ‘prompt’ mode
[NO ACTION]
[SWITCH OFF]
[PROMPT MODE]
Number of EXTRA HOUR
button presses allowed in
‘Prompt’ mode
bP 1HR BOOSTS uL uL,
1 to 99
uL = unlimited number,
1…99 = specified number of button
presses, after which unit switches off
[NUM BOOSTS]
Enable telephone call
number display
tC SHOW
PHONE
0 0, 1 0 = disabled
1 = enabled
[DISABLED]
[ENABLED]
Enter telephone STD code St STD CODE ------- 1 When a
or button is first pressed the LoT™ Display
shows a row of dashes which can be adjusted using or
buttons, then verified using the button.
Enter telephone number nU NUMBER --------- 1 When a
or button is first pressed the LoT™ Display
shows a row of dashes which can be adjusted using or
buttons, then verified using the button.
* Reset ‘SET SERVICE’
parameters to default values
rS ALRM RESET 1 0,1 0 = do not reset
1 = default parameters
[NO RESET]
[RESET]
* This parameter by default has a value of 1, unless any other parameter is adjusted, when it will change to 0. Set it to 1 to reset all parameters
back to defaults
Set Service parameters are listed in the table below, along with a description of the options that are possible.
or
LoT™ Display
Parameter
Number
Parameter
Value
3.4 Installer Setup Flowchart