Instruction Manual
Microprocessor Temperature Regulator HT MC11
Page 11 of 22
S o . S t Softstart
(Softstart) >PID<
OFF
Softstart function not active.
Softstart parameters are not displayed.
on
Softstart function is active.
S o . y Softstart output
ratio (Softstart y) >PID<
Range: 10 … 100 % <30>
S o . S P Softstart Setpoint
>PID<
Range: S P . Lo S P . Hi <0>
S o . t i Softstart duration
time >PID<
Range: OFF ; 0.1 … 10.0 min <1.0>
C o . S P Configuration
Setpoint (setpoint selection)
S P . I
Setpoint 1
S P . 2
Setpoint 2
S P . E
External setpoint
rE C . 2 2nd parameter set
(record 2)
- -
Not adjusted
S P . 2
Save actual parameters as 2nd parameter set
S P . E
Load 2nd parameter set as actual parameters
The second parameter set can be used to store and – if necessary to restore follow-
ing actual parameters: control parameters, setpoints and setpoint configuration,
process offset, ramps, softstart and alarm configuration.
The factory setting of the second parameter set is identical to the actual parameter
set.
H A n d
Operating mode of the regula-
tor
(Manual mode)
<PID>
OFF
Controller mode
Au t o
Auto-
matic
mode
In case of a sensor break, the regulator mode is au-
tomatically changed to “ manual mode” using the
last valid output ratio.
Manual mode is indicated with a leading "H" in
the setpoint display, followed by the output ratio.
The output ratio can be changed manually.
In following cases the output ratio is 0 %:
if the output ratio was 100 % at the time of the
sensor break
if a setpoint ramp is active
if the control deviation from the measuring
range was > 0.25% at the time of the sensor
break
if parameter P (xp) = 0 (OFF)
if softstart was active at the time of the sensor
break
A few seconds after the sensor break has been rec-
tified, the controller returns to automatic operation
and calculates the required output ratio.
Alarm contact 1 can be programmed to activate an
additional signal in case of sensor break.
m
An
Manual
mode
Device operates as a power controller. Temperature
regulation function is not active.
"PROCESS display" shows the actual process value.
SETPOINT display” shows a leading "H" followed
by the actual adjustable output ratio.
Negative value: cooling, positive value: heating
The output ratio can be changed manually.
Version 1080/1.03 02/2018
471 11 400
Horst GmbH
Bitzenheimer Weg 10
D-64653 Lorsch
Telefon: +49 (0) 6251 9626 0
Telefax: +49 (0) 6251 9626 96
Only displayed if
S o . S t = o n
External setpoint adjustments
0..10 VDC = measuring range of
the adjusted sensor (page 9)