EasyManua.ls Logo

Hoval TopVent TH-6C - Pump Control for Mixing or Injection System

Hoval TopVent TH-6C
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.11 Pump control for mixing or injection system
Instead of the diverting system, a mixing or injection circuit can also be installed in
the load circuit.
Please note the following:
Not only the mixing valves but also the pumps in the load circuit are controlled
directly by the control block.
Terminals for wiring the mixing valves and the pumps in the load circuit are
located in the connection box.
Make sure that valves and pumps which meet the following requirements are
provided on site.
Requirements for mixing valves
Use 3-way mixing valves with the following ow characteristics:
Equal percentage control path
Linear bypass
The valve authority must be ≥ 0.5.
The maximum run time of the valve actuator is 45 s.
The valve actuator must be continuous, i.e. the stroke changes in proportion to
the control voltage (0…10 V DC or 2…10 V DC).
The valve actuator must be designed with a position response (0...10 V DC or
2…10 V DC).
The maximum power consumption is 20 VA.
Install the valve close to the unit (max. distance 2 m).
Requirements for pumps
Voltage ..........230 V AC
Current ..........up to 4.0 A
Requirements on changeover valves
Use changeover valves conforming to the following specication:
3-way changeover valves
Supply voltage 24 V AC
1-wire control (0/24 V AC)
Position response via limit switches (0°/90°)
Power consumption max. 44 VA
24
TopVent
®
TH
|
TC
|
THC
|
MH
|
MC
|
MHC
Operating instructions
Options
4 218 828-en-01 4 218 828-en-01