Howden 24-07.030r04 21/25
E-series Axial Flow Cooling Fans
Power absorption (too)
high. (2)
Static pressure higher than
specified.
Clean system air-cooler
bundles or cooling tower
fill.
Air temperature lower than
design air temperature.
Check performance
against current air tem-
perature.
Set blade angle according
fan selection details.
Transmission out of order.
Impeller is rubbing against
fan casing.
Bolting of drive-train con-
nection, support structure
or fan housing is not tight.
Decrease impeller diame-
ter by placing nylon rings
between lower clamping
pieces and blade stem
collars.
Vibration level high. (1)
Check if position of fan
blades is according to in-
struction.
Lack of stiffness in support
structure.
Reinforce support struc-
ture.
Bolting of drive-train con-
nection or fan housing is
not tight.
Drive alignment incorrect.
Drainage holes are
blocked.
Blade is not flush against
lower clamping piece.
Release U-bolts, pull the
blade outwards and re-
tighten the U-bolts to the
correct torque.
Blade angle(s) not within
±0.5° tolerance.