Diagnostics and Troubleshooting
Compaq ProLiant DL360 Server Maintenance and Service Guide 4-9
COMPAQ CONFIDENTIAL Codename: MIcroMachines Part Number: 169616-006 Last Saved On: 12/21/01 9:05 AM
Table 4-2: POST Error Messages
Error Code Audible Beeps
Probable Source of
Problem Recommended Action
A Critical Error
occurred prior to
this power-up
None A catastrophic system
error, which caused the
server to crash, has been
logged.
Run Diagnostics. Replace
failed assembly as indicated.
Unsupported
Processor
Detected System
Halted
1 long, 1 short Processor not supported by
current system ROM.
Check Chapter 2, “Removal
and Replacement Procedures,”
Table 2-4 for supported
processors, and if supported,
remove the processor and
update the system to latest
ROM.
FATAL ROM
ERROR: The
System ROM is
not properly
programmed
1 long, 1 short ROM programmed in
factory incorrectly.
Replace the physical ROM
part.
101-ROM Error 1 long, 1 short System ROM checksum Run Diagnostics. Replace
failed assembly as indicated.
101-I/O ROM
Error
None Options ROM checksum Run Diagnostics. Replace
failed assembly as indicated.
102-System
Board Failure
None DMA, timers, and so on Replace the system board.
Run the Compaq System
Configuration Utility.
104-ASR-2 Timer
Failure
None System board failure Run Diagnostics. Replace
failed assembly as indicated.
162-System
Options Not Set
2 short Configuration incorrect Run the System Configuration
Utility and correct.
163-Time & Date
Not Set
2 short Invalid time or date in
configuration memory
Run the System Configuration
Utility and correct.
continued