NOTE: PDU models can be changed in the field using offline maintenance procedures.
NOTE: When ordering systems, HP does not allow mixtures of different phase PDUs in a system
(even though there are no technical issues). Only upgrade orders can ship with difference phase
PDUs in a system.
Figure 23 P9500 AC power configuration diagram
Environmental specifications
The following table lists the environmental specifications of the P9500 storage system.
Table 31 P9500 environmental specifications
In StorageNot OperatingOperatingItem
-45 - 140-18 - 109.4 / -10 to 4360.8 - 80.9 /Temperature
-25 to 60-18 to 95 / -10 to 35
8
16 to 32(ºF / ºC)
5 to 958 to 9020 to 80Relative Humidity
(%)
2
84.2 / 2980.6 / 2778.8 / 26Max. Wet Bulb
(ºF / ºC)
68 / 2050 / 1050 / 10Temperature
Deviation
per hour)
(ºF / ºC)
Sine Vibration:5 to 10 Hz: 2.5 mm10 to 300 HzVibration
4.9 m/s
1
, 5 min.10 to 70 Hz: 4.9 m/s
1
0.49 m/s
1
to 10Hz: 0.25 mm
Environmental specifications 83