21
881629-001
ENGLISH
6. Technical specifications
6.2 INTL technical specifications
Tower HPE T750 G5 INTL Tower HPE T1000 G5 INTL Tower HPE T1500 G5 INTL Tower
Output power @ 230 V
750 VA
600 W
1000 VA
770 W
1440 VA
1100 W
Output power @ 208 V
750 VA
600 W
1000 VA
770 W
1440 VA
1100 W
Output power @ 200 V
625 VA
500 W
833 VA
641 W
1080 VA
825 W
AC input power
• Rated input voltage Single phase 200–240 V
• Input voltage range
160 to 294 V
(1)
• Input frequency range
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on Battery Power
• Voltage
200/208/220/230/240 V (-10%/+6%)
(3)
• Frequency 50/60 Hz ±0.1 Hz
Battery (sealed lead-acid, maintenance free)
• Standard 2 x 12 V
7 Ah
2 x 12 V
9 Ah
3 x 12 V
9 Ah
Environment
• Operating
temperature range
0°C to 35°C
(32°F to 95°F)
0°C to 40°C
(32°F to 104°F)
• Storage
temperature range
-15°C to +50°C
(5°F to 122°F)
• Relative humidity 20% to 90% (without condensation)
• Noise level <40 dBA
(1) The high and low thresholds can be adjusted using UPS settings.
(2) Up to 40 Hz in Low-Sensitivity mode (programmable using UPS settings).
(3) Adjustable to 200/208/220/230/240 V, must be set to the identical AC power source value.
CAUTION: This UPS is rated for use on a circuit capable of delivering no more than 5 kRMS symmetrical
amperes, 240 V maximum.
When the appliance is used in EU areas, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant.
When the appliance is used in American areas, use an external circuit breaker in front of line with rating
20 A, 250 V.
This product is designed for IT power distribution systems.
Filter
Transformer
"AVR"
Charger Inverter
Battery