TL-LFP Series liFePO
4
Battery Operation Manual
Table 2.1, and LVBD is larger than 41.0V.
Voltage drop on cable between battery module and power plant shall be less than 0.5V.
4.7 – Storage
4.7.1 Storage Requirements
1. Place modules according to the signs on the packing case during storage. Do not put modules
upside down or sidelong.
2. Stack modules packing cases by complying with the stacking requirements on the external
package.
3. The storage environment requirements are as follows:
− Ambient temperature: 0–40°C; recommended storage temperature: 20–30°C
− Relative humidity:
≤
95%
− In a dry clean place with proper ventilation
− In a place that is away from corrosive and organic substances (including gas)
− In a place free from direct sunlight
− At least 2 meters away from heat sources (such as a heater)
4. The warehouse keeper should collect TL-LFP modules storage information every month and
periodically report the modules inventory information to the planning department. The modules
that have been stored overdue should be recharged in a timely manner.
5. The modules should be delivered based on the "first in, first out" rule.
6. Install modules in a dry, clean, and ventilated environment that is free from sources of strong
infrared radiation, organic solvents, and corrosive gases. Do not expose the modules to sunlight
or water and keep them far away from sources of ignition.
4.7.2 Judgement Conditions for Overdue Storage
The battery storage shall be in the clean and dry ventilation room at the temperature of 0~40°C.
It is recommended that the modules should not be stored for a long period.
Actual Storage
Temperature
Not reaching the time for recharge: Use the module
as soon as possible.
Reaching the time for recharge: Recharge the
module.
Note:
1. storage battery over 45°C or under 0°C will reduce battery life.
2.The storage duration (t) starts from the latest charge time on the module. The latest charge
time is updated after every charge.
3.If an module is qualified after charge, mark the latest charge time and the next recharge time
on the module packing case. The next recharge time is 8 months (stored above 30°C) or 12
months (stored below 30°C) later than the latest charge time. The total storage duration should