EasyManua.ls Logo

HST HP101 - 2.5 Zone Installation

HST HP101
17 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 2.3 - Batteries wiring connection
2.5 Zone Installation
The panel has either 4, 8 or 16 class B conventional input zones. Wire the smoke, heat
or multi detector positive terminals to the terminal labeled +” and the negative
detector terminals to the terminal labeled “-“ as shown in figure 2.4 which shows the
panel. Each active zone requires a 4K7end of line (EOL) resistor at the very end of
the zone as shown in figure 2.4.
Figure 2.4 - Detectors wiring connection
2.6 NAC (Sounder) Output Circuit Installation
The control panel has 2 built-in output notification appliance circuits (NAC).
Figure 2.5 shows output circuit 1 wired as a class B NAC output. Observe the
polarity of the wiring and the placement of the 10K end of line (EOL) resistor located
at the very end of the class B wiring.
Figure 2.5 – Sounder/bell wiring connection
2.7 Relay Outputs
Each panel has 2 forms C relays, the relays are dedicated to common alarm (auxiliary
contacts) and common fault functions. All 2 relay outputs (Alarm and fault relays)
carry the same voltage and current ratings. The relays are rated 2 amps at 30VDC.
- 10 -
4K7
EOL
SENSE ZONES(DETECT/CALL POINTS)
+1- +2- +3- +4- +5- +6- +7- +8-
--_
in + out+
in – out-
in – out-
in + out+
10K/1W