LP-743 Rev. 000 Rel. 000 Date 8.25.20
17
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
34 - 40 7 4 Floor drying cycle
0 = OFF
1 = Functional Heating
2 = Curing Heating
3 = Functional Heating + Curing Heating
4 = Curing Heating + Functional Heating
5 = Manual
0
34 - 40 7 5 Floor dry Supply setpoint temperature 77 - 140°F 131
34 - 40 7 7
Burning Hours Harmonization
Sets the burner run hours statistics to equal the average of the other boilers in the cascade. Used when replacing the
PCB on a Follower boiler. Perform this function ONLY on the boiler where the PCB has just been replaced.
34 - 40 8 RESET MENU
34 - 40 8 0
Automatically resets all parameters to the
factory defaults.
WARNING: Always check PCB settings
if restoring factory default settings on a
replacement controller. Replacement controllers
have generic settings that may not be specic to
the boiler model.
Reset: OK = yes, ESC = no
Only applicable to parameters in menu level 34-40 of respective Follower boiler.
34 - 40 10 OTHERS 2
34 - 40 10 0 NOT USED
34 - 40 10 1
DHW Modulation Setpoint 68 - 179
o
F 179
Boiler target temperature during a DHW demand. Not applicable for WCN models.
34 - 40 10 2
DHW On Dierential Temperature 0 - 36
o
F 0
Determines how much the DHW storage tank temperature can drop below target before initiating a DHW demand. Only
applicable when 2.2.8 = 1.
34 - 40 10 3
Emergency Setpoint 68 - 179
o
F 113
Sets Follower boiler operating temperature when communication with the Master is lost, or when the System Sensor is
disconnected. See Cascade Instruction Manual.
34 - 40 10 4 NOT USED
34 - 40 10 5 NOT USED
34 - 40 10 6 NOT USED
34 - 40 50 BOILER STATISTICS - 1 - READ ONLY
34 - 40 50 0 3 way valve cycles No. (n x10)
34 - 40 50 1 Boiler Pump On Hours (h x10)
34 - 40 50 2 Boiler pump cycles No. (n x10)
34 - 40 50 3 Boiler Power On Time (h x10)
34 - 40 50 4 Fan On Hours (h x10)
34 - 40 50 5 Number of fan cycles (n x10)
34 - 40 50 6 CH number of ame detections (n x10)
34 - 40 50 7 DHW number of ame detections (n x10)
34 - 40 51 BOILER STATISTICS - 2 - READ ONLY
34 - 40 51 0 CH Burner On Hours (h x10)
34 - 40 51 1 DHW Burner On Hours (h x10)
34 - 40 51 2 Number Of Flame Faults (n x10)
34 - 40 51 3 Number Of Ignition Cycles (n x10)