LP-293 Rev. 9.24.15
12
Chlorine concentration less than 100 ppm
Using chlorinated fresh water should be acceptable as
levels are typically less than 5 ppm.
Do not connect the boiler to directly heat swimming
pool or spa water.
Do not ll boiler or operate with water containing
chlorine in excess of 100 ppm.
Figure 4 - Boiler Dimensions - NOTE: All Dimensions Are Approximate
*NOTE: It is recommended to clean the heat exchanger at
least once a year to prevent lime scale buildup. To clean the
heat exchanger, follow the maintenance procedure in this
manual.
Hardness: Less than 7 grains
Chloride levels: Less than 100 ppm
pH levels: 6 - 8
TDS: Less than 2000 ppm
Sodium: Less than 20 mGL